E33.0.31.6C-02     Manual for connection and operation of the GIR230 Pt1000 / DIF and GIR230 NTC /DIF          Page 4 of 14
2. Introduction
GIR230 Pt1000 / DIF and the GIR230 NTC / DIF  is a microprocessor controlled displaying, monitoring and
controlling device.
The device is supporting two interface for the connection of:
- Pt1000 (2-wire-technology) 
at type GIR230 Pt1000 / DIF
  - NTC (2-wire-technology) 
at type GIR230 NTC / DIF
The display and regulation will occur to the difference (sensor 1 – sensor 2)
of the both measuring inputs.
The device features three switching outputs (2 * Relays, 1 * NPN-Output), which can be configured as 2-
point-controller, 3-point-controller, 2-point-controller with min./max. alarm, 3-point-controller with min./max.
alarm, or just individual min./max. alarm.
The state of the relay outputs is displayed with two LED’s beneath the front 4-digit LED-display. The left LED
displays the state of the 1st relay, the right LED displays the state of the 2nd relay.
If there is an alarm condition the display alternates between value and AL.Lo or AL.Hi.
When leaving factory the GIR230 has been subjected to various inspection tests and is completely cali-
brated.
Before the GIR230 can be used, it has to be configured for the customer’s application.
Hint: In order to avoid undefined input states and unwanted or wrong switching processes, we sug-
gest to connect the device’s switching outputs after You have configured the device properly.
3. Electrical connection
Wiring and commissioning of the device must be carried out by skilled personnel only.
In case of wrong wiring the device may be destroyed. We can not assume any warranty in case of
wrong wiring of the device.
3.1.  Terminal assignment
1
Relay-output 2 (230V
AC)
2
Relay-output 1 (230V
AC)
3
Supply voltage, 230V
AC
4
Supply voltage, 230V
AC
5
Output 3
6
GND
7
temperature sensor 2
8
temperature sensor 1
3.2. Connection data
typical
limitations
between
terminals
min.
max.
min.
max.
notes
Supply voltage
3 and 4
207 V
AC
244 V
AC
0 V
AC
253 V
AC
Relay outputs 1 and 2
1 and 3,
2 and 3
5 A,
ohm resistive load
Output 3
(NPN, open collector)
5 and 6
0 V
DC
28 V
DC
,
I < 30mA
Input temperature sensor
6 and 8,
7 and 8,
6 and 7
0 Ω
∞ Ω
No active signal allowed
These limits must not be exceeded (not even for a short time) !
678
5
1234
Rel 1
Rel 2
230 V ~
230 V ~
Out 3
GND
Se
ns
or
  1
Se
ns
or
 2