Entes MPR-63 Mains-analysis device, Mains analyser MPR-63 사용자 설명서

제품 코드
MPR-63
다운로드
페이지 47
Net (Network Type)
The network type is set in this menu.
3P4W
:
3 Phase + Neutral (Star connection)
3P3W
:
 3 Phase without Neutral (Delta connection)
ARON :
ARON connection.
          NOT : In 3P3W connections, as the neutral point is not connected, V
LN
 voltages could be monitored
          different on unbalanced voltages.
4.1  SETUP
In order for correct measurements and applications, make necesarry configurations in the SETUP menu.
Sub-menus under the SETUP menu and settings are explained in detail below.
4.2  Network
In this menu, current transformer primary value, voltage transformer ratio and system connection type of device are
set.
It has 5 sub-menus.
“CT:…..”,  “VT:……”,  “Net:……”, “Eng:........”, “E.Unit:.......”
CT (Current Transformer Ratio)
The current transformer 
ratio
 is set between 1...5000.
20
Figure 11: 
Setting the current transformer ratio
Figure 12: 
Setting the voltage transformer ratio
Eng
If “Tot” menu is selected, device measures the reactive powers of the phases. If the total reactive power of the
phases is inductive, it is recorded to the inductive area; If capacitive, it is recorded to the reactive area. If “Sprt”
menu is selected, device measures the reactive powers of three phases for each phase seperately. If it is in
the inductive area, it is recorded to the inductive reactive area. If it is in the capacitive area, it is recorded to
the capacitive reactive area.
Measurement for each phase seperately can be done for 3P4W (3 Phase with Neutral) systems.
Figure 14: 
Setting the energy calculation type
Figure 13: 
Setting the type of system connection
VT (Voltage Transformer Ratio)
The voltage transformer ratio can be adjusted between 1.0...4000.0
Please be careful that this value must be the voltage transformer ratio but not the value of the primary or
secondary voltage.
4. GENERAL MENU
It is used for determine the units of energy counters. Counters can be chosen Mega or Kilo.
for example :
 If energy counter value is 12345678901 kWh
when
“k”
is chosen, 45678901 kWh will be displayed or
when
“M”
is chosen, 12345678 MWh will be displayed.
E.Unit: (Energy Unit)