Fluke 1652C05-TPOLEKITVDE-tester 4426016 사용자 설명서
제품 코드
4426016
Electrical
Installation
Tester
Specifications
45
General Specifications
Specification Characteristic
Size
10 cm (L) x 25 cm (W) x 12.5 cm (H)
Weight (with batteries)
1.3 kg
Battery size, quantity
Type AA, 6 ea.
Battery type
Alkaline supplied.
Usable with 1.2 V NiCd or NiMH batteries (not supplied)
Usable with 1.2 V NiCd or NiMH batteries (not supplied)
Battery life (typical)
200 hours idling
Fuse
T3.15 A, 500 V, 1.5 kA 6.3 x 32 mm (PN 2030852)
Operating Temperature
-10
°
C to 40
°
C
Storage Temperature
-10
°
C to 60
°
C indefinitely (to -40
°
C for 100 hrs)
Relative Humidity
80 % 10 to 35
°
C; 70 % 35 to 40
°
C
Operating Altitude
0 to 2000 meters
Shock, Vibration
Vibration to Class 3 per Mil-Prf-28800F
1 meter drop test, six sides, oak floor
1 meter drop test, six sides, oak floor
Sealing
IP 40
EMC
Complies with EN61326-1: 2006
Safety
Complies with EN61010-1 Ed 2.0 (2001-02), UL61010,
ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2
No.1010 2
ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2
No.1010 2
nd
edition
Overvoltage Category: 500 V/CAT III
300 V/CAT IV
Measurement Category III is for measurements
performed in the building installation. Examples are
distribution panels, circuit breakers, wiring and cabling.
Category IV equipment is designed to protect against
transients from the primary supply level, such as an
electrical meter or an overhead or underground utility
service.
Performance EN61557-1, EN61557-2, EN61557-3,
EN61557-4, EN61557-5, EN61557-6, EN61557-7
Second edition. EN61557-10 First edition.
performed in the building installation. Examples are
distribution panels, circuit breakers, wiring and cabling.
Category IV equipment is designed to protect against
transients from the primary supply level, such as an
electrical meter or an overhead or underground utility
service.
Performance EN61557-1, EN61557-2, EN61557-3,
EN61557-4, EN61557-5, EN61557-6, EN61557-7
Second edition. EN61557-10 First edition.
Pollution Degree
2
Maximum voltage between any
terminal and earth ground
terminal and earth ground
500 V
Surge Protection
6 kV peak per EN 61010-1 Ed. 2.0 (2001-02)