Faber Kabel Grey 020323 데이터 시트
제품 코드
020323
DBL_NI2XY.PDF Issue 26.09.2014 Klaus Faber AG, 66113 Saarbrücken, Lebacher Str. 152-156, Tel.: (0681) 9711-0, FAX: - 289
Installation cable NI2XY
acc. to VDE 0262
conductor material:
bare copper
insulation:
XLPE
sheathing material:
PVC
colour of outer sheath:
grey
flame retardant:
VDE 0482-332-1-2/IEC 60332-1
UV-resistant:
yes
max. operating temperature,
fixed:
-40 - +90 °C
temperature, moved/during
installation:
-5 - +90 °C
bending radius, fixed
installation:
4 x DA
nominal voltage Uo:
600 V
nominal voltage U:
1 kV
test voltage:
4 kV
core identification:
colours acc. VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers
Application: Inside of buildings, at the surface, inside or under plaster in dry and moist rooms an outdoor (not inside
water or the earth).
water or the earth).
The products and information presented here are for technical calculation only. They are subject to technical progress and in no way represent the
ability of shipment. Outer diameters are approximately.
Table: Technical characteristics
p/n
part name
R
l
.
[Ω/km]
D
A
.
[mm]
Cu
.
[kg/km]
G
.
[kg]
020322
NI2XY-J 03X1,5 0,6/1 kV GR
12,1
8,9
43,2
122
020323
NI2XY-J 05X1,5 0,6/1 kV GR
12,1
10,5
72
160
020324
NI2XY-J 03X2,5 0,6/1 kV GR
7,41
9,8
72
170
020325
NI2XY-J 05X2,5 0,6/1 kV GR
7,41
11,5
120
228
Rl
conductor resistance
DA
outer diameter
Cu
copper
G
weight