Technical data
General
Weight
340 g
Mounting type
Wall mounting
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
24 V supply (bus logics) / FE
Test section
24 V supply (bus logics) / Digital inputs (sensor supply) 500 V AC
50 Hz 1 min
Test section
24 V supply (bus logics) / Digital outputs (actuator supply) 500 V
AC 50 Hz 1 min
Test section
FE / Digital inputs (sensor supply) 500 V AC 50 Hz 1 min
Test section
FE / Digital outputs (actuator supply) 500 V AC 50 Hz 1 min
Test section
Digital inputs (sensor supply) / Digital outputs (actuator supply)
500 V AC 50 Hz 1 min
Interfaces
Fieldbus system
CANopen
®
Name
CANopen
®
Connection method
2 M12 connectors, A-coded
Transmission speed
10, 20, 50, 125, 250, 500, 1000 kBit/s (Automatic baud rate
detection)
Transmission physics
Copper cable with optional power supply in acc. with CAN
standard
Address area assignment
1 ... 126, adjustable
Number of positions
5
Power supply for module electronics
Connection method
M12 connector, (A-coded)
Name
U
L
Supply voltage
24 V DC
Supply voltage range
18 V DC ... 30 V DC IEC 61131-2 (including ripple)
Fieldline potentials
Voltage supply U
L
24 V DC
Power supply at U
L
max. 4 A
Current consumption from U
L
typ. 60 mA
Current consumption from U
L
max. 100 mA
Voltage supply U
S
24 V DC
Power supply at U
S
max. 4 A
Current consumption from U
S
typ. 10 mA (plus sensor current)
Current consumption from U
S
max. 500 mA
Voltage supply U
A11
24 V DC
Power supply at U
A11
max. 4 A
Current consumption at U
A11
typ. 6 mA (plus actuator current)
Current consumption at U
A11
max. 4 A
Voltage supply U
A12
24 V DC