Nov 14, 2013    3 / 8
Technical data
Protective circuit
Short-circuit current self-quenching
100 A (effective (N-PE))
Follow current quenching capacity If (L-N)
50 kA (264 V AC)
Follow current quenching capacity If (L-N)
25 kA (350 V AC)
Follow current quenching capacity If (N-PE)
100 A
Connection, protective circuit
Connection method
Screw terminal blocks
Connection type IN
Biconnect screw terminal block
Connection type OUT
Biconnect screw terminal block
Connection method
Biconnect terminal block
Screw thread
M5
Tightening torque
4.5 Nm
Stripping length
18 mm
Conductor cross section stranded min.
2.5 mm²
Conductor cross section stranded max.
25 mm²
Conductor cross section solid min.
2.5 mm²
Conductor cross section solid max.
35 mm²
Conductor cross section AWG/kcmil min.
13
Conductor cross section AWG/kcmil max
2
Remote indicator contact
Connection name
Remote fault indicator contact
Switching function
PDT contact
Connection method
Plug-in/screw connection via COMBICON
Screw thread
M2
Tightening torque
0.25 Nm
Stripping length
7 mm
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
1.5 mm²
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section AWG/kcmil min.
28
Conductor cross section AWG/kcmil max
16
Maximum operating voltage U
max.
 AC
250 V AC
Maximum operating voltage U
max
 DC
125 V DC
Max. operating current I
max
1 A AC (inductive)
Max. operating current I
max
1 A AC (ohmic)
Max. operating current I
max
30 mA DC (inductive)
Max. operating current I
max
200 mA DC (ohmic)
Min. permissible switching capacity
0.12 VA (12 V, 10 mA)
Standards and Regulations
Standards/regulations
IEC 61643-1 2005