B B Thermotechnik B & B Thermotechnik CON-REGME 12 V 12/24V Rain Detector In Housing Dry/humid or fog detection CON-REGME 12 V 데이터 시트

제품 코드
CON-REGME 12 V
다운로드
페이지 2
DATA SHEET
Technical changes reserved
Connection
After removing the sensor cover, the control cable is to be inserted in
the cable gland M16.
Supply voltage is to be connected to the terminals VCC and GND.
Terminals NC, COM, NO are the potential free changeover contacts 
for switching.
Precautions:
•  The device is suitable only for low voltages and should not be 
operated on mains supply !
•  The relay contact is only suitable for low value signals and 
should not come in contact with mains supply !
•  The protection type is valid only with an intact, complete casing, 
cover screws and cable gland properly tightened, and the cover-
gasket should always be available on the sensor cover !
•  The suitability for certain applications is to be checked by the 
user
Settings
Signal generator output (optional)
At the connection terminals (Pin BUZ and GND) a passive Piezo 
signal generator can be connected. The condition of signal (acustic 
signal for dry or wet) can be selected with the plug links S1-S2 or 
S2-S3. In the default-position S2-S3, the signal generator is inactive 
for rain.
Switching mode
The switching mode of the relay (pickup or dropout with rain) can be
selected with the plug links T1-T2 or T2-T3. In the factory settings, 
link T1-T2 is connected and the relay closes if the sensor surface 
gets wet.
Heating
The sensor surface is heated, if the link of HZ1-HZ2 is connected. To
ensure faster drying and for operation below freezing point, the 
heater should be switched on. For sensing fog, the heater can be 
switched off.
Sensitivity setting
The sensitivity to moisture signal can be adjusted through the 
potentiometer. Rotating the potentiometer knob in the anti clockwise 
direction gives higher sensitivity ( left = high sensitivity, right = low 
sensitivity). For normal rain signal, the middle position is most suitab-
le. Please note that no function takes place in the end position!
Indicators
There is a green LED on the device to indicate the operation status 
and a red LED to indicate the switch position (meansrelay contact 
closed).
Maintenance
The Rain Sensor unit is almost maintenance free. The sensor surface
must be occasionally cleaned with a moist cloth ( e.g. once annually,
depending on the place of installation). In case of persistent condi-
tion, even if it does not rain, it triggers due to strong contamination.
Connection Layout
REL NC 
Opening switch contact
REL NO 
Closing switch contact
REL CO 
Common switch contact
AC/DC 
Operating voltage AC or 24 V DC +10%
AC/GND 
Operating voltage AC or 0 V
Plug Links Configuration
S3 
Switch mode signal generator (dry)
S2 
Common contact to S3 and S1
S1 
Switch mode signal generator (wet)
GND 
Signal generator ground
BUZ 
Signal generator output
T3 
Switch mode relay (dry)
7
T2 
Common contact to T3 and T1
T1 
Switch mode relay (wet)
HZ1 
Heating
10
HZ2 
Heating
factory setting: S3 - S2, T1 - T2, HZ1 - HZ2
Dimensions
Accessoires
wall / mast mounting bracket
including mouting hardware
Rain Detector REGME
model 12V AC/DC or 24V AC/DC
B+B Thermo-Technik GmbH | Heinrich-Hertz-Straße 4 | D-78166 Donaueschingen 
Fon +49 771 83160 | Fax +49 771 831650 | info@bb-sensors.com | bb-sensors.com
2 / 2