RED LIGHT: waiting f or programming
GREEN LIGHT: done
LED ROSSO: acceso in programmazione
LED VERDE: programmazione eseguita
Parameters and setpoint values can be copied from one device to
another using the Memory card
There are two methods:
insert the memory card
.
On activation display 1 shows and display 2 shows
The device loads the new data and starts again
The memory card is equipped with an internal battery with a life of about 1000 uses.
Insert the memory card and press the programming button.
When writing the parameters, the LED turns red and on completing the procedure
it changes to green. It is possible to repeat the procedure.
To
the memory card values, follow the procedure described in the first
method, setting display 2 to
so as not to load the parameters on controller.
Enter configuration and
.
Exit configuration. Changes are saved automatically.
With the counter connected to the power supply
when the counter is off
With the counter disconnected from the power supply:
change at least one parameter
update
.
(Only if the values stored on Mmeory Card are correct).
By pressing the
key display 2 shows
Confirm using the
key .
.
Attention: Pls. perform first an update of the
memory card
>
>
UPDATING MEMORY CARD.
INTRODUCTION
Thanks for choosing a Wachendorff Prozesstechnik device.The VZ484801 can
be set in 2 different modes: Single or Double counter, all with independent
settings. 3 universal digital inputs are available (NPN/PNP/Potential free
contact) and can be used for bidirectional encoders reading, UP/DOWN counter
function, LOCK/HOLD to lock or hold current visualization.One input is also
analogue in order to allow setpoint modification by an external potentiometer.
Potentiometer:
1
2
3
4
To modify Set1 or Set2 by external potentiometer follow the steps below:
- use potentiometers 0 to 5/ 10kohm
- connect cursor to pin I3; a wrong connection may damage the potentiometer and
lead to lock of the device.
- accuracy on input is max 1000 points, therefore set the parameters "Upper limit"
and "Lower limit" with a max difference of 1000 units.
(Ex.: LoS1 to 50,0 and uPS1 to 150,0 to modify time value related to Set1 between
50 and 150 seconds with steps of one tenth). Greater differences would make
unstable the less significant digit.
- To calibrate the scale of potentiometer enter the configuration mode and select:
Hin.3 as Pot Fin.3 as Set1 or Set2 P.tAr as Enable
Exit configuration mode and place potentiometer at minimum level and press
key,
then place potentiometer at max level and press premere
key: the device
automatically exit the calibration procedure.
N.B.: A switch-off of the device would interrupt the calibration.
MEMORY CARD (optional)
MEMORY CARD (optional)
P-01 Counter Function
FUNCTION CONFIGURATION
P-02 Power-off Memory
BACKUP MEMORY CONFIGURATION
Counter functions
1 counter functioning
Power-off memory
No counter stored at power-off
Default
Default
Single (1 Counter)
Double (2 Counters)
Counter 1 stored at power-off
Counter 2 stored at power-off
All counters stored at power-off
2 counters functioning
P-03 Hardware input 1
INPUT CONFIGURATION
Input 1 hardware configuration
NPN (not available on input 3)
Default
PNP
TTL
Potentiometer (available only for input 3)
P-04 Hardware input 2
Input 2 hardware configuration
P-05 Hardware input 3
Input 3 hardware configuration
P-06 Filter Delay Input 1
Input 1 digital filter configuration
Input filter desabled
Default
Filter of 0,5 ms
...(Step 0,5 ms)
P-07 Filter Delay Input 2
Input 2 digital filter configuration
P-08 Filter Delay Input 3
Input 3 digital filter configuration
Filter of 100,0 ms
P-09 Active State Input 1
Active state input 1
P-10 Active State Input 2
Active state input 2
Disabled
Default
Loading counter 1
Loading counter 2
Loading counters 1 and 2
P-13 Function Key UP
Function associated to UP (up arrow key)
Disabled
Default
Enabled
P-14 Potentiom. Tarature
Potentiometer calibration procedure
Disable
Enable
Disabled
Default
Loading encoder Z
Loading counter 1
Loading counter 2
P-12 Function Input 3
Function associated to input 3
Loading counters 1 and 2
Set1 setting by potentiometer
Set2 setting by potentiometer
High level (available only for input 1)
Default
High Level
Low Level
Rising edge
Falling edge
Low level (available only for input 2)
Rising edge
Falling edge
COUNTER CLOCK CONFIGURATION
Disabled
Default C2
Disable
Encoder
I1 Up, I2 Off
I1 Down, I2 Off
Bidirectional encoder (I1) phase A, (I2) phase B
UP mode (I1)
DOWN mode (I1)
P-15 Clock Counter 1
Counter 1 count mode selection
P-33 Clock Counter 2
Counter 2 count mode selection
Default C1
I1 Off, I2 Up
I1 Off, I2 Down
I1 Up, I2 Down
I1 Up, I2 Incr./Decr.
I1 Up, I2 En./Lock
I1 Up, I2 En./Hold
I1 Down, I2 En./Lock
I1 Down, I2 En./Hold
Output Counter 2/1
UP mode (I2)
DOWN mode (I2)
UP mode (I1) - DOWN mode (I2)
UP mode (I1) with reverse direction (I2)
UP mode (I1) with count lock (I2)
UP mode (I1) with keeping value on display (I2)
DOWN mode (I1) with count lock (I2)
DOWN mode (I1) with keeping value on display (I2)
UP count on rising edge of counter 2/1
COUNTER DISPLAY CONFIGURATION
Counter value not visualized
Default C2
Counter value visualized
P-16 Display Counter 1
Counter 1 visualization selection
P-34 Display Counter 2
Counter 2 visualization selection
Default C1
Disable
Visualized
No decimal digit visualization
Default
1 decimal digit visualization
2 decimal digits visualization
3 decimal digits visualization
P-17 Decimal Point Counter 1
P-35 Decimal Point Counter 2
Default
P-17 Decimal Point Counter 1
Counter 1 visualization format
P-35 Decimal Point Counter 2
Counter 2 visualization format
P-18 Counter 1 input counts
Counter 1 input counts (1...9999)
P-36 Counter 2 input counts
Counter 2 input counts (1...9999)
Default 1
Default 1
P-19 Counter 1 Visualized Counts
Counter 1 visualized counts (1...9999)
P-37 Counter 2 Visualized Counts
Counter 2 visualized counts (1...9999)
Default 1
Default 1
SETPOINT CONFIGURATION
Setpoint value not visualized
Default C2
Setpoint value visualized
P-20 Display Set 1
Counter 1 setpoint visualization selection
P-38 Display Set 2
Counter 2 setpoint visualization selection
Disable
Visualized
Modifiable
Setpoint value visualized and modifiable
Default C1
P-21 Lower Limit Set 1
Set 1 minimum value (0...9999)
P-39 Lower Limit Set 2
Set 2 minimum value (0...9999)
Default 0
Default 0
P-22 Upper Limit Set 1
Set 1 maximum value (0...9999)
P-40 Upper Limit Set 2
Set 2 maximum value (0...9999)
Default 999
Default 999
Automatic loading desabled
Default
Loading if counter = Set1
Loading if counter = Set2
Loading if counter = Set1 + “Output Duration 1”
P-23 Automatic Load Counter 1
Counter 1 automatic loading
Loading if counter = Set2 + “Output Duration 2”
Loading if counter = “Visualized Counts”
P-41 Automatic Load Counter 2
Counter 2 automatic loading
AUTOMATIC LOAD CONFIGURATION
COUNTER LOAD VALUE CONFIGURATION
P-24 Counter Load Value 1
Counter 1 loading value
P-42 Counter Load Value 2
Counter 2 loading value
Default 0
Default 0
Default
Output active if Counter Set
=
Output active for “Output Duration” time if Counter Set
=
Output active for “Output Duration” counts if Counter Set
=
P-25 Counter 1 Output Mode
P-43 Counter 2 Output Mode
Default
Counter 1 output mode
Counter 2 output mode
COUNTER OUTPUT MODE CONFIGURATION
P-46 Decimal Point Frequency Counter 2
P-28 Decimal Point Frequency Counter 1
COUNTER FREQUENCY DISPLAY CONFIGURATION
Counter frequency value not visualized
Default
Counter frequency value visualized
P-27 Display Frequency Counter 1
Counter 1 frequency visualization
P-45 Display Frequency Counter 2
Counter 2 frequency visualization
Disable
Visualized
Default
0
0.0
0.00
0.000
Visualization with 2 decimal digits
Visualization with 3 decimal digits
Visualization with no decimal digit
Default
Visualization with 1 decimal digit
Counter 1 frequency format
Counter 2 frequency format
P-29 Counter 1 Input frequency
Counter 1 input frequency (1...9999Hz)
P-47 Counter 2 Input frequency
Counter 2 input frequency (1...9999Hz)
Default 1
Default 1
P-30 Counter 1 Visualized Frequency
Counter 1 visualized frequency
Default 1
P-48 Counter 2 Visualized Frequency
Counter 2 visualized frequency
Default 1
P-31 Output Q1 Setup
Output Q1 settings
P-32 Output Q2 Setup
Output Q2 settings
Disabled output
Default C1
Disable
Out Counter 1 n.o.
Out Counter 1 n.c.
Out Counter 2 n.o.
Out Counter 2 n.c.
Counter 1 output on n.o. contact
Counter 1 output on n.c. contact
Counter 2 output on n.o. contact
Counter 2 output on n.c. contact
Default C2
Output active if Counter Set1+Set2
=
Default
Latch output resettable by counter loading
Output duration minimum value
Output duration maximum value
P-26 Output 1 Duration
P-44 Output 2 Duration
Value modifiable by user
Default 10
Counter 1 output duration
Counter 2 output duration
OUTPUT DURATION CONFIGURATION
Default 10
P-11 Active State Input 3
Active state input 3
SIZE AND INSTALLATION
SIZE AND INSTALLATION
48
mm
48 mm
46 x 46 mm
Frontal panel cut-out
2
mm
Suggested thickness
÷ 6
106 mm
10
A 3
MAN
TUN
REM
C 1
C 1
C 2
C 2
A 1
A 2
1
6
Memory Card
1
5
2
3
4
5
4
3
2
1
I3
10
9
8
7
6
SUPPLY
24...230V
AC/DC
8A 230V
Resistive
1/2HP
CAUTION
Risk
of
Electric
Shock
Disconnect
power
supply
before
servicing
I2
I1
OUT 24V
Q2
8A 230V
Resistive
1/2HP
Q1
MEMOR
Y
C
.241
MEMOR
Y
C.241
PRESS
Display 1 shows
with 1°digit blinking, while
Display 2 shows
DISPLAY
DO
or
Modifies blinking digit and
pass to the next one pressing
Enter password
to confirm
Device loads default values
Switch the device off
and restart it
1
2
3
LOADING DEFAULT VALUES
LOADING DEFAULT VALUES
SET for
3 seconds
PRESS
Display 1 shows
with first digit blinking, while
Display 2 shows
DISPLAY
DO
or
Modifies blinking digit and
pass to the next one pressing
Enter password
to confirm
Display shows first parameter of
configuration table
1
2
3
Scroll paremeters
4
or
Increase or decrease visualized value
pressing
and an arrow key
Enter the new data
that will be saved
when releasing arrow key
5
+
or
End configuration, controller
exits from programming mode
6
MODIFY CONFIGURATION PARAMETERS
MODIFY CONFIGURATION PARAMETERS
SET for
3 seconds
+
PARAMETERS LIST
PARAMETERS LIST
Disable
Encoder Z
Load Counter 1
Load Counter 2
Load Counter 1&2
Set1
Set2
Disable
Load Counter 1
Load Counter 2
Load Counter 1&2
Disable
Counter 1
Counter 2
All Counters
NPN
PNP
TTL
Potent.
No delay
0,5 ms
...
100,0 ms
Output Duration Input by User
Latch output (clear only by load)
Min output duration
Max output duration
Disable
Counter = Set 1
Counter = Set 2
Counter = Set 1+Output Duration 1
Counter = Set 2+Output Duration 2
Counter = Visualized counts
Counter Set
Counter Set * Output Duration (time)
Counter Set * Output Duration (counts)
Counter Set1+Set2
=
=
=
=
0
0.0
0.00
0.000
WIRING DIAGRAM
WIRING DIAGRAM
GND
POSITIVO
Fase Z
Encoder
Fase B
Fase A
5
4
3
2
1
I3
10
9
8
7
6
SUPPLY
24...230V
AC/DC
8A 230V
Resistiv
1/2HP
CAUTION
Risk
of
Electric
Shock
Disconnect
power
supply
before
servicing
I2
I1
OUT 24V
Q2
8A 230V
Resistiv
1/2HP
Q1
NPN
5
4
3
2
1
I3
10
9
8
7
6
SUPPLY
24...230V
AC/DC
8A 230V
Resistiv
1/2HP
CAUTION
Risk
of
Electric
Shock
Disconnect
power
supply
before
servicing
I2
I1
OUT 24V
Q2
8A 230V
Resistiv
1/2HP
Q1
PNP
PNP
NPN
5
4
3
2
1
I3
10
9
8
7
6
SUPPLY
24...230V
AC/DC
8A 230V
Resistiv
1/2HP
CAUTION
Risk
of
Electric
Shock
Disconnect
power
supply
before
servicing
I2
I1
OUT 24V
Q2
8A 230V
Resistiv
1/2HP
Q1
POTENTIOMETER 0..5/10 Kohm
Accuracy 1.000 points
5
4
3
2
1
I3
10
9
8
7
6
SUPPLY
24...230V
AC/DC
8A 230V
Resistiv
1/2HP
CAUTION
Risk
of
Electric
Shock
Disconnect
power
supply
before
servicing
I2
I1
OUT 24V
Q2
8A 230V
Resistiv
1/2HP
Q1
-
+
OUTPUT
5
4
3
2
1
I3
10
9
8
7
6
SUPPLY
24...230V
AC/DC
8A 230V
Resistiv
1/2HP
CAUTION
Risk
of
Electric
Shock
Disconnect
power
supply
before
servicing
I2
I1
OUT 24V
Q2
8A 230V
Resistiv
1/2HP
Q1
Proximity
Sensor PNP
3 wires
Proximity
Sensor PNP
2 wires
I1
I2
I3
I1
I2
I3
PRESS
Visualizes SETPOINT 1 / 2
DISPLAY
or
Modify selected SET
1
2
SETPOINT MODIFICATION
SETPOINT MODIFICATION
Report the activation of Q1
MEANING
Report the activation of Q2
LED
Report serial transmission by the VZ484801
A 3
MAN
MAN
TUN
REM
C 1
C 1
C 2
C 2
A 1
A 2
A 3
MAN
MAN
TUN
REM
C 1
C 1
C 2
C 2
A 1
A 2
A 3
MAN
TUN
REM
C 1
C 1
C 2
C 2
A 1
A 2
Operating conditions
Sealing
Material
Digital Inputs
Outputs
OUT 24V
Back-UP
Power Supply
TECHNICAL DATA
TECHNICAL DATA
Operating temperature 0-40°C, humidity 35..95uR%
Front panel IP65 (with gasket),
IP20 box and terminal blocks
PC ABS UL94V0 self-extinguishing
3PNP/NPN configurable as analogue for potentiometers.(max 28
Vdc in PNP mode)
2 relays 8A resistive charge
.
Rechargeable battery, approx. 60 days autonomy
24...230Vac/Vdc +/-15% 50/60Hz / 2W
30mA(at 24 VAC supply),40 mA(at 24 VDC supply),
60 mA (at 110 to 230 VAC)
Wachendorff Prozesstechnik GmbH & Co. KG www.wp-direkt.de
e-mail: RSS@wachendorff.de
Version 2.0
MANUAL COUNTER
VZ484801
MANUAL COUNTER
VZ484801
CN1
1
6
Read carefully the safety guidelines and programming instructions contained in
this manual before using/connecting the device.Disconnect power supply before
proceeding to hardware settings or electrical wirings.Only qualified personnel
should be allowed to use the device and/or service it and in accordance to
technical data and environmental conditions listed in this manual.Do not dispose
electric tools together with household waste materials in observance of
European Directive 2002/96/CE
LOADING DEFAULT VALUES
This procedure restores the factory settings of the instrument.