Operating Manual
TRITEST
®
 pro
Before using the TRITEST
®
 pro phase sequence 
indicator:
Please read the operating manual and absolutely 
observe the safety instructions!
Table of contents
1. Safety instructions
2. Device description
3. Functional test
4. Phase sequence test
5. LED torch
6. Battery replacement
7. Technical data
8. General maintenance
9. Environmental protection 
1. Safety instructions
-  During the tests, touch the device at the insulated 
test probes 9,   and  only and do not touch 
the bare testing electrodes 8! 
-  Check the device for correct functioning immedi-
ately before and after using it (see section 3)! Do 
not use the device, if one or more indications are 
not working or if it does not seem to be ready for 
operation!
-  If it is assumed that safe operation is no longer 
possible, the device must be switched off immedi-
ately. 
-  Absolutely prevent the device from getting wet 
and avoid any water condensation at the device. 
Moreover, the device must be protected against 
contamination and damaging! 
-  The device must be used within the stated nomi-
nal voltage range and in electrical installations of 
up to 500 V AC only! 
-  The device must be used only in electric circuits 
of overvoltage category CAT III with max. 300 V 
for phase-to-earth measurements. For measure-
ments within measuring category III, the protrud-
ing conductive part of a testing electrode 8 of the 
test probe must not be longer than 4 mm. Before 
carrying out measurements within measuring cat-
egory III, the enclosed attachable protective caps 
marked with CAT III must be pushed onto the test-
ing electrodes 8 for user protection purposes.
-   Please observe that work on live parts and elec-
trical components of all kinds is dangerous! Even 
low voltages of 30 V AC and 60 V DC may be 
dangerous to human life!
-   Do not operate the device with the battery com-
partment being open.
-  The device is designed for being used by qualified 
electricians and under safe working conditions. 
-   Do not dismantle the device! 
Attention!
The device is provided with a high-power LED torch. 
Do not look directly or indirectly via reflecting surfaces 
into the LED beam. An LED beam might cause irrepa-
rable damage to your eyes.
Symbols on the device: 
Symbol
Meaning
Attention! Please observe documenta-
tion!
This symbol indicates that the informa-
tion provided in the operating manual 
must be complied with in order to avoid 
risks.
Alternating voltage (AC)
Earth (voltage to earth)
This symbol shows the orientation of the 
batteries for inserting them with correct 
polarity.
Warning! Potentially dangerous optical 
radiation!
Do not look directly into the light beam! 
Danger to your retina!
Attention! Magnets might affect the cor-
rect functioning of cardiac pacemakers 
and implanted defibrillators. As a user of 
such medical devices, keep a sufficient 
distance to the magnet.
2.  Device description
1
  Red LED for external conductor (phase) L1
2
  Red LED for external conductor (phase) L2
3
  Red LED for external conductor (phase) L3
4
  Red LED for counter-clockwise phase sequence
5
  Green LED for clockwise phase sequence
6
  High-power LED torch 
7
 Push-button
8
  Testing electrodes with attachable protective caps
9
  Test probe L1 (brown), part no.: 10112582
  Test probe L2 (black), part no.: 10112581
  Test probe L3 (grey), part no.: 10112584
  Alligator clip, part no.: 709269
  Catch of the battery compartment cover
  Battery compartment cover with magnet, belt clip 
and technical data
3.  Functional test
-  Check the device for correct functioning immedi-
ately before and after using it! 
-  Test the correct functioning of the LEDs 1,  2 
and  3 for indicating the external conductors L1, 
L2 and L3 as well as the LEDs 4 and 5 of the 
phase sequence indication with a familiar voltage 
source, e.g. a 400 V CEE socket.
-  Do not use the device, if not all functions are 
working properly!
-  Please replace the batteries as soon as the lumi-
nosity of the LED torch 6 decreases.
4.  Phase sequence test
-  Connect the connecting cables marked with L1, 
L2 and L3 to the mains to be tested. For this pur-
pose, use the test probes 9,  and  or the alli-
gator clip . 
-  The external conductor voltages are indicated by 
means of the red LEDs 1, 2 and 3.
-  Depending on the connection, the red LED (4) for 
"counter-clockwise phase sequence" or the green 
LED  5 for "clockwise phase sequence" will be 
activated.
-  Interchanging the test probes on two external 
conductors must result in a change of the phase 
sequence.
-  For each test, make sure that all three external 
conductor voltages are present. Only then, the 
indicated results can be analyzed!
tritest-pro_d3.indd   3
24.10.2014   09:08:45