Secutech Radio modules ST002004 데이터 시트

제품 코드
ST002004
다운로드
페이지 40
Page 22
 
Security & Electronic Technologies GmbH
 
 
 
Connections of the barrier SECU-BAR 125 
 
IN
OUT
U  = 18 V ... 36 V DC
in
U  = 24 V
I  = 125 mA
out
out
 
 
Application hints: 
SECU-DATA instruments which are to be installed in Ex-zone 1 have to be 
supplied  from  an  intrinsically  safe  power  supply  to  ensure  the  ignition  pro-
tection  as  per  ATEX  (directive  94/9/EC)  EN  60079-0,  and  EN  60079-11. 
The  not  intrinsically  safe  power  supply  with  a  permissible  voltage  range  of 
18  …  36  V  is  connected  to  the  input  IN  of  the  barrier  SECU-BAR  125. 
SECU-BAR  125  limits  the  output  voltage  to  max.  25.2  V  and  the  output 
current to max. 131.3 mA. The intrinsically safe output OUT is connected to 
the power supply terminals of a SECU-DATA xxxx device.