Technical data
Input data
Setting range for min. input current
0 A ... 0.2 A
Setting range for max. input current
0 A ... 11 A
Impulse form
AC, DC or distorted currents
Overload capacity
2 x I
N (
continuous)
Surge strength
20 x I
N
 (1 s)
Frequency measuring range
15 Hz ... 400 Hz
Connection method
Screw connection
Output data
Output name
Voltage output / current output
Configurable/programmable
Yes, unconfigured
Voltage output signal
0 V ... 10 V
Voltage output signal
2 V ... 10 V
Voltage output signal
-10 V ... 10 V
Voltage output signal
0 V ... 5 V
Voltage output signal
1 V ... 5 V
Voltage output signal
-5 V ... 5 V
Voltage output signal
10 V ... 0 V
Voltage output signal
10 V ... 2 V
Voltage output signal
10 V ... -10 V
Voltage output signal
5 V ... 0 V
Voltage output signal
5 V ... 1 V
Voltage output signal
5 V ... -5 V
Current output signal
0 mA ... 20 mA
Current output signal
4 mA ... 20 mA
Current output signal
20 mA ... 0 mA
Current output signal
20 mA ... 4 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω
Switching output
Output name
Relay output
Contact type
1 PDT
Contact material
AgSnO, hard gold-plated
Maximum switching voltage
30 V AC
Maximum switching voltage
36 V DC
Maximum switching voltage
250 V AC (when the gold layer is destroyed)
Limiting continuous current
50 mA
Limiting continuous current
2 A (when the gold layer is destroyed)
Output name
Transistor output, pnp
Output voltage range
19 V ... 29 V (supply voltage - 1 V)
Continuous load current
80 mA (Not short-circuit proof)