Panasonic AKT7212100J Digital Temperature Controller AKT7212100J 데이터 시트

제품 코드
AKT7212100J
다운로드
페이지 20
16 
Input     
 
Thermocouple  : K, J, R, S, B, E, T, N, PL- , C (W/Re5-26)    External resistance; 100  or less 
However, for thermocouple B, external resistance, 40  or less 
 
RTD 
: Pt100, JPt100, 3-wire system 
                           Allowable input lead wire resistance (10   or less per wire) 
 
DC current 
: 0 to 20mA DC, 4 to 20mA DC, input impedance 50  
[Connect 50   shunt resistor (AKT4811, sold separately) between input   
terminals 5 and 6] 
Allowable input current: 50mA or less 
 DC 
voltage 
 
 
 
 
0 to 1V DC 
0 to 5V DC, 1 to 5V DC, 
0 to 10V DC 
Input impedance 
1M  or more 
100k  or more 
Allowable input voltage
5V or less 
15V or less 
Allowable signal source
resistance 
2k  or less 
100  or less 
 
Accuracy (Setting and Indication) 
 
Thermocouple
: Within 
0.2% of input span 
1 digit, or within 
2  (4 ) whichever is greater 
                     However, for R, S input, 0 to 200  (0 to 400 ): Within 
6  (12 ) 
           B input, 0 to 300   (0 to 600 ): Accuracy is not guaranteed. 
 
K, J, E, T, N input, less than 0  (32 ): Within 
0.4% of input span 
1 digit 
                          RTD 
: Within 
0.1% of input span 
1 digit, or within 
1  (2 ) whichever is greater 
 
DC voltage    : Within 
0.2% of input span 
1 digit 
 
DC current 
: Within 
0.2% of input span 
1 digit 
 
Input sampling period: 0.25 seconds 
Control     
Control action 
• PID action (with auto-tuning function) 
• PI action: When derivative time is set to 0 
• PD action (with manual reset function): When integral time is set to 0 
• P action (with manual reset function): When derivative and integral time are set to 0 
• ON/OFF action: When proportional band is set to 0 
              OUT proportional band  : 0.0 to 110.0% (ON/OFF action when set to 0.0) 
 
Integral time 
  : 0 to 1000 seconds (Off when set to 0)   
 
Derivative time 
: 0 to 300 seconds (Off when set to 0) 
 
OUT proportional cycle  : 1 to 120 seconds 
 
ARW      
: 0 to 100%  
 Manual 
reset 
Proportional band converted value 
 
Output limit 
: 0 to 100% (DC current output type: –5 to 105%) 
 
(Not available for ON/OFF action) 
 Hysteresis 
Thermocouple, RTD input: 0.1 to 100.0   ( ) 
 
DC voltage, current input: 1 to 1000 
 
(The placement of the decimal point follows the selection) 
Control output (OUT) 
• Relay contact: 1a, Control capacity   3A  250V AC (Resistive load) 
 
1A    250V AC (Inductive load COS ø =0.4) 
Electrical life, 100,000 cycles 
• Non-contact voltage (for SSR drive): 12
+2
  0
V DC    Max. 40mA (Short circuit protected) 
 DC current: 4 to 20mA DC, Load resistance; Max. 550  
Output accuracy: Within 
0.3% of output span 
Resolution : 
12000 
EVT output   
 
 Alarm output   
[Alarm, Loop break alarm and Heater burnout alarm (option) utilize common output terminals.] 
The alarm action point is set by 
  deviation from the SV (excluding Process alarm) 
and when input is out of the alarm setting range, alarm (EVT) turns ON or OFF (High/Low limit   
range alarm). When Deenergized is selected in the Energized/Deenergized selection, alarm 
(EVT) is activated conversely. 
Setting accuracy 
: The same as indication accuracy 
Action 
: ON/OFF action 
Hysteresis : 
Thermocouple, RTD input: 0.1 to 100.0 ( ) 
            
DC voltage, current input: 1 to 1000 (The placement of the decimal 
 
point follows the selection) 
Output 
: Open collector, Control capacity 24V DC    0.1A (Max.) 
Alarm type 
: One alarm type is selectable from below by front keypad operation: 
 
High limit, Low limit, High/Low limits, High/Low limit range, Process high, 
 
Process low, High limit with standby, Low limit with standby, 
 
High/Low limits with standby and No alarm action