5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
252
 
Operating Instructions, 06/2014 
Depending on your configuration of the Q parameter, the output is either reset with a reset 
signal at input R or Ral ("Q  →  R"), or when the reset signal is 1 or the En signal is 0 ("Q  →  
R+En"). 
Viewing the MI, MN and OT values 
In LOGO!Soft Comfort you can fetch the hours counter via the Tools -> Transfer -> Hours 
Counter (Page 85) menu command. 
Limit value of OT 
The value of the operating hours in OT is retained when you reset the hours counter with a 
signal at input R. The hours counter OT will be reset to zero with a transition from 0 to 1 at 
Ral. The hours counter OT continues the count as long as En = 1, irrespective of the status 
at the reset input R. The counter limit of OT is 99999 h. The hours counter stops when it 
reaches this value.  
In programming mode, you can set the initial value of OT. MN is calculated according to the 
following formula when reset input R is never enabled: MN = MI - (OT % MI). The % operator 
provides an integer division remainder. 
Example: 
MI = 30h, OT = 100h 
MN = 30 - (100 % 30) 
MN = 30 -10 
MN = 20h 
 
In runtime mode, the value OT cannot be preset. If the value for MI is changed, there would 
be no calculation for the MN. MN would take on the value of MI. 
Parameter preset 
In LOGO!Soft Comfort, you can define MI and an OT start value. 
You determine that Q does not depend on En by selecting the corresponding check box. 
Retentivity with the hours counter 
The hours counter in the LOGO! is retentive. 
If the values of the hours counter are lost after a power failure, then select the respective 
block in your circuit program. Right-click the hours counter and select Block Properties > 
Parameter. The option Retentivity must be activated and unchangeable (grayed out).