LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 06/2014, A5E33039675 
159
 
4.4.11 
Weekly timer 
Short description 
The weekly timer controls an output by means of a configurable on/off date. The function 
supports any combination of weekdays. You select the active weekdays by hiding the 
inactive days.  
 
 
Note 
Because LOGO! 24/24o does not have a real-time clock, the weekly timer function is not 
available. 
 
 
 
Symbol in LOGO!  Wiring 
Description 
 
Cam parameters 
1, 2 and 3 
At the Cam parameters, you set the on- and off-times of the 
weekly timer for each Cam switch. Here you also configure 
the days and the time-of-day. 
You can also specify whether the timer pulses on for one 
cycle when activated and then reset. The pulse setting 
applies to all three cams. 
Output Q 
LOGO! sets Q when actuating the configured cam. 
Timing diagram (three examples) 
 
Functional description 
Each weekly timer has three cams for you to configure a time hysteresis. You specify the on- 
and off-times at the Cam parameters. The weekly timer sets the output at a certain on-time; 
if you have not set it, the weekly timer resets the output at a certain off-time if you configure 
an off-time, or at the end of the cycle if you specify a pulse output.  
You will cause a conflict if you set overlapping on- and off-times; the earliest on- and off- 
times take priority. Here is an example: 
 
Cam 
On-time 
Off-time 
1:00h 
2:00h