LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 06/2014, A5E33039675 
187
 
Timing diagram B: Function with positive difference Δ 
 
Functional description 
The function fetches the analog signal at input Ax.  
Ax is multiplied by the value of the A (gain) parameter, and the value at parameter B (offset) 
is added to product, i.e. (Ax • gain) + offset = actual value of Ax. 
Output Q is set or reset, depending on the set (On) threshold and difference value (Δ). The 
function automatically calculates the Off parameter: Off = On + Δ, whereby Δ may be 
positive or negative. See the calculation rule below. 
Calculation rule 
●  When you set a negative differential value Δ, the On threshold ≥ Off threshold, and Q = 
1if the actual value Ax > On or Q = 0 if the actual value Ax ≤ Off.  
See the timing diagram A. 
●  When you set a positive differential value Δ, the On threshold < the Off threshold, and Q 
= 1, if On ≤ actual value Ax < Off. 
See the timing diagram B. 
Setting the Par parameter 
The gain and offset parameters are used to adapt the sensors to the relevant application. 
View in programming mode (example): 
 
View in parameter assignment mode (example):