LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 06/2014, A5E33039675 
217
 
Symbol in LOGO! 
Wiring 
Description 
Parameter 
Level 1 and Level 2:  
levels to be reached 
Range of values for each level:  
-10000 to 20000 
MaxL: 
maximum value that must not be exceeded under any 
circumstances. 
Range of values: -10000 to 20000 
StSp: 
Start/Stop offset: value that is added to Offset "B" to 
create the start/stop level. If the Start/Stop offset is 0, 
then the start/stop level is Offset "B". 
 Range of values:  
 0 to 20000 
Rate: 
acceleration with which level 1, level 2 or Offset is 
reached. Steps/seconds are issued. 
 Range of values:  
 1 to 10000 
A: gain 
 Range of values:  
 0 to 10.00 
B: offset 
 Range of values:  
 -10000 to 10000 
p: number of decimals 
 Range of values: 
 0, 1, 2, 3 
Output AQ 
Range of values for AQ: 
0 to 32767 
(Current Level - Offset "B") / Gain "A" 
Range of values: 
0 to 32767 
Note: 
When AQ is displayed in parameter mode or 
message mode, it is displayed as a scaled value, 
both on the LOGO! Base Module and LOGO!Soft 
Comfort (engineering units: current level). 
Parameters L1, L2 
The analog values for the parameters L1 and L2 can be derived from another already-
programmed function. You can use the actual values of the following functions:  
●  Analog comparator (Page 188) (actual value Ax – Ay) 
●  Analog threshold trigger (Page 183) (actual value Ax) 
●  Analog amplifier (Page 195) (actual value Ax) 
●  Analog multiplexer (Page 213) (actual value AQ) 
●  Mathematic instruction (Page 227) (actual value AQ)