Wago 750-457 Fieldbus Independent I/O Module 750-457 데이터 시트

제품 코드
750-457
다운로드
페이지 1
750-457, 750-459 / 753-457, 753-459
Subject to design changes
WAGO Kontakttechnik GmbH & Co. KG
Postfach 2880 •D-32385 Minden Tel.: +49(0)571/887-0
E-Mail: info@wago.com
25.04.2007
Hansastr. 27 •D-32423 Minden Fax: +49(0)571/887-169 www.wago.com
4-Channel Analog Input Module ±10 V/0-10 V
single-ended (S.E.)
Fig. Series 750 / Technical data see page 30 / Delivery without Mini WSB marker 
Series 750 / 753 marking see pages 20 ... 21 / 22 ... 23
AI 2 
Data contacts 
Common 
(ground) 
Common 
(ground) 
 
AI 1 
Common 
(ground) 
AI 4 
Power jumper contacts 
AI 3 
Common 
(ground) 
 
AI 3 
AI 1 
Error 
AI 4 
AI 2 
Error 
E1  E2 
13 14 

M M 
750-457 
E3  E4 
M  M 
AI 2 
AI 4 
AI 1 
Common 
(ground) 
24 V 
AI 
Common 
(ground) 
Logic 
Error 
270pF   
10nF 
AI 3 
0 V 
Common 
(ground) 
750-457 

 

 

 

 
 
 
 
 
The analog input module receives signals with the standardized values 
±10 V and 0-10 V.
The input signal is electrically isolated and will be transmitted with a resolution 
of 12 bits.
The internal system supply is used for the power supply of the module.
The input channels of a module have one common ground potential.
Description
Item no.
Pack. 
unit
4AI ±10V DC S.E.
750-457
10 
1)
4AI 0-10V DC S.E.
750-459
10 
1)
4AI ±10V DC S.E. (without connector)
753-457
10 
1)
4AI 0-10V DC S.E. (without connector)
753-459
10 
1)
1)
 Also available individually
Accessories
Item no.
Pack. 
unit
Connectors 
Connectors Series 753
753-110
25
Coding elements
753-150
100
Miniature WSB Quick marking system
plain
248-501
5
with marking
see pages 214 ... 215
Approvals
Series 750 and 753
r
 UL 508
 
Conformity marking
1
Series 750
Marine applications
see pages 24 ... 27
4
 EN 50021
II 3 G EEx nA II T4
4
 r UL 1604
Class I Div2 ABCD T4A
Technical Data
No. of inputs
4
Voltage supply
via system voltage DC / DC
Current consumption (internal)
65 mA
Input voltage max.
± 40 V
Signal voltage
± 10 V (750-457, 753-457)
0 V ... 10 V (750-459, 753-459)
Input resistance
> 100 kΩ
Resolution
12 bits
Conversion time typ.
10 ms
Measuring error (25°C)
< ± 0.2 % of the full scale value
Temperature coefficient
< ± 0.01 % / K of the full scale value
Isolation
500 V system / supply
Bit width
4 x 16 bits data 
4 x 8 bits control / status (optional)
Wire connection
CAGE CLAMP
®
Cross sections
0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Stripped length series 750 / 753
8 ... 9 mm / 0.33 in
9 ... 10 mm / 0.37 in
Width
12 mm
Weight
approx. 55 g
EMC 1-Immunity to interference
acc. to EN 50082-2 (1996)
EMC 1-Emission of interference
acc. to EN 50081-1 (1993)
EMC marine applications - 
Immunity to interference
acc. to Germanischer Lloyd (2001)
EMC marine applications - 
Emission of interference
acc. to Germanischer Lloyd (2001)