1. Application 
 
ÖLFLEX
®
 SOLAR XLS-R cables are weather-, abrasion- and UV-resistant photovoltaic cables. These cross-linked, halogen 
free and double insulated solar cables are suitable for permanent outdoor use and especially for the interconnection of 
grounded and ungrounded photovoltaic power systems. They are applicable for the connection of solar panels among them-
selves and as extension cable between the individual module strings or the DC/AC inverter.  
 
 
2. Cable design 
 
                 
 
 
1. Conductor:  
 
 
Fine wire strands of tinned copper according to IEC 60228, Class 5 
 
2. Core insulation:  
Temperature resistant and halogen free polyolefine co-polymer,  
electron beam cross-linked 
 
     
 
 
 
Colour: white, red or blue 
 
  
3. Outer sheath:  
 Flame retardant, weather resistant and halogen free polyolefin co-polymer,  
 
 
 electron beam cross-linked, 
 
     
 
 
 
Outer sheath colour: black 
 
 
3. Electrical properties 
 
Rated voltage U
0
/U acc. IEC 
 
AC 600/1000 V 
DC 900/1500 V   
Max. permissible operating voltage  
DC 1800 V (conductor/conductor, non earthed system) 
 
Test voltage 
 
 
 
AC 6,5 kV 
 
 
4. Thermal properties 
 
 
Temperature range  
 
 
fixed installation: -40 °C up to +100 °C  
(max. conductor temperature according to IEC 60216) 
 
High temperature pressure resistance 
according EN 60811-3-1 
 
Damp heat resistance 
 
 
according EN 60068-2-78 at 85% humidity 
 
 
 
5. Mechanical properties 
 
Minimum bending radius   
 
occasional flexing: 15 x cable diameter 
 
 
 
 
 
fixed installation:      5 x cable diameter 
Dynamic penetration resistance 
 
according DKE requirement specification PV1-F AK 411.2.3 Annex F 
Notch propagation resistance 
 
according DKE requirement specification PV1-F AK 411.2.3 Annex G 
Tensile strength and elongation 
 
 
of insulation and jacket 
 
 
according EN 60811