Omron G7Z-3A1B-11Z 24 VDC Mini Connectors G7Z Wit 40 A Contact G7Z-3A1B-11Z 24 VDC 3 NO closed contact/1 NO open contact G7Z-3A1B-11Z 24 VDC 데이터 시트

제품 코드
G7Z-3A1B-11Z 24 VDC
다운로드
페이지 8
3
G7Z
Characteristics
Note: The above values are initial values. 
*1. The contact resistance for the Relay (G7Z) was measured with 1 A at 5 VDC using the voltage drop method. 
The contact resistance for the auxiliary contact block (G73Z) was measured with 0.1 A at 5 VDC using the voltage drop method. 
*2. The operate time was measured with the rated voltage imposed with any contact bounce ignored at the ambient temperature of 23°C. 
*3. The insulation resistance was measured with a 1,000-VDC megohmmeter applied to the same places as those used for checking the dielectric 
strength. 
*4. The electrical endurance was measured at an ambient temperature of 23°C. 
*5. The specifications for the auxiliary contact block mounted on the G7Z are the same as those for the G73Z auxiliary contact block. 
*6. The failure rate is based on an operating frequency of 1,800 operations/h.
Approved Standards
UL Standard: UL508, UL840 (File No. E41643) 
* Auxiliary contact ratings 
CSA Standard: CSA Certification by 
 : CSA C22.2 No. 14
EN Standard/TÜV Certification: EN 60947-4-1 
(Certification No. R50079155)
* Auxiliary contact ratings
< Reference > Information
UL 508:
Industrial control devices 
UL 840:
Insulation coordination including clearance and 
creepage distance for electrical devices 
CSA C22.2 No. 14: Industrial control devices 
EN 60947-4-1:
Contactors 
Classification
Relay 
*5
Auxiliary contact block
Item
Model
G7Z-4A-
@Z, G7Z-3A1B-@Z, G7Z-2A2B-@Z
G73Z-20Z, G73Z-11Z, G73Z-02Z
Contact resistance 
*1
400 m
Ω max.
100 m
Ω max.
Operating time 
*2
50 ms max.
Release time 
*2
50 ms max.
Maximum operating 
frequency
Mechanical
1,800 operations/h
Rated load
1,200 operations/h
Insulation resistance 
*3
1,000 M
Ω min.
Dielectric strength
Between coil and contacts 
4,000 VAC, 50/60 Hz for 1 min 
---
Between contacts of different polarity 
4,000 VAC, 50/60 Hz for 1 min 
Between contacts of the same polarity  2,000 VAC, 50/60 Hz for 1 min 
Impulse withstand 
voltage 
Between coil and contacts 
10 kV, 1.2 
× 50 µs
---
Between contacts of different polarity 
10 kV, 1.2 
× 50 µs
Between contacts of the same polarity  4.5 kV, 1.2 
× 50 µs
Vibration resistance
Destruction
10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude) 
Malfunction
NO: 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude) 
NC: 10 to 32 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude) 
Shock resistance
Destruction
Screw mounting: 700 m/s
2
, DIN Track mounting: 500 m/s
2
 
Malfunction
NO: 100 m/s
2
 
NC: 25 m/s
2
  
Durability
Mechanical
1,000,000 operations min. (at 1,800 operations/h, contact no load) 
Electrical 
*4
AC resistive load: 80,000 operations 
AC inductive load: 80,000 operations 
DC resistive load: 100,000 operations 
(at 1,200 operations/h, rated load)
Failure rate (P level) (reference value) 
*6
2 A at 24 VDC
1 mA at 5 VDC
Ambient operating temperature
−25 to 60°C (with no icing or condensation) 
Ambient operating humidity
5% to 85% 
Weight
Approx. 330 g
Approx. 18 g
Model
Coil 
ratings
Contact ratings
Number of 
test 
operations
G7Z
12, 24 VDC
NO 
contact 
40 A, 480 VAC, 60 Hz 
(Resistive)
80,000
5 A, 120 VDC (Resistive)
100,000
22 A, 480 VAC, 60 Hz 
(General Use)
100,000
D300
* (1-A current applied)
---
NC 
contact
25 A, 480 VAC, 60 Hz 
(Resistive)
5 A, 120 VDC (Resistive)
10 A, 480 VAC, 60 Hz 
(General Use)
100,000
D300
* (1-A current applied)
---
Model
Contact ratings
G73Z
NO contact 
D300 (1-A current applied)
NC contact
Model
Coil ratings
Contact ratings
G7Z
12, 24 VDC
NO 
contact 
AC-1: 40 A, 440 V, 50/60 Hz
AC-3: 16 A, 440 V, 50/60 Hz
DC-1: 5 A, 110 V
*AC-15: 0.5 A, 440 V, 50/60 Hz
*DC-13: 0.5 A, 110 V
NC 
contact
AC-1: 25 A, 440 V, 50/60 Hz
DC-1: 5 A, 110 V
*AC-15: 0.5 A, 440 V, 50/60 Hz
*DC-13: 0.5 A, 110 V
G73Z
---
NO 
contact 
AC-15: 0.5 A, 440 V , 50/60 Hz
DC-13: 0.5 A, 110 V
NC 
contact