Gnb Sonnenschein GF 12 040 Y, 12V Ah lead acid battery 8889765000 8889765000 데이터 시트

제품 코드
8889765000
다운로드
페이지 18
            
                                                                         
Edition: Sept. 2014
 
 
 
The Master document is located electronically. Printed copies of this document are not controlled, unless identified as such. The USER has to assure the document is valid prior to use. 
4.   First Aid measures 
This information is of relevance only if the Battery is broken and this results in a direct contact with the 
ingredients. 
4.1    General 
        Electrolyte (diluted sulphuric acid):     sulphuric acid acts corrosively and damages skin 
        Lead compounds:                              lead compounds are classified as toxic for reproduction  
                                                                   (if  swallowed) 
4.2  Electrolyte (Sulphuric acid) 
        after skin contact:                               rinse with water, remove and wash wetted clothing 
        after inhalation of acid mist:               inhale fresh air, seek advice of a medical doctor 
        after contact with the eyes:                rinse under running water for minimum 15 minutes, seek 
                                                                   advice of a medical doctor 
        after swallowing:                                drink lot of water immediately, swallow activated carbon, do  
                                                                   not induce vomiting, seek advice of a medical doctor 
4.3  Lead compounds 
         after skin contact:                               clean with water and soap 
         after contact with the eyes:                rinse under running water for minimum 15 minutes, seek 
                                                                   advice of a medical doctor 
                   
5.   Fire fighting measures 
Suitable fire extinguishing agents: 
        CO
2
 or dry powder extinguishing agents 
Unsuitable fire extinguishing agents: 
        Water, if the battery voltage is above 120 V 
Special protective equipment: 
        Protective  goggles,  respiratory  protective  equipment,  acid  protective  equipment,  acid-proof  
         clothing in case of larger stationary battery plants or where larger quantities are stored.    
     
6.   Measures to be taken in case of accidental release 
This information is of relevance only if the battery is broken and the ingredients are released. 
In the case of spillage, use a bonding agent, such as sand, to absorb spilled acid; use lime / sodium 
carbonate  for  neutralisation;  dispose  of  with  due  regard  to  the  official  local  regulations;  do  not  allow 
penetration into the sewage system, into earth or water bodies. 
 
7.   Handling and Storage 
Store under a roof in cool ambient temperature range, for fully charged lead-acid batteries the range is 
from  -40  up  to  +60ºC.  If  batteries  have  the  possibility  to  remain  discharged  in  cold  conditions,  a 
correction to the lower temperature limit is recommended to prevent freezing:  
 
 -30ºC at 75% state of charge, 
 
 -20ºC at 50% state of charge, 
 
 and -10ºC at 25% state of charge;  