Configuration and programming 
 
5.4 Programming the telecontrol instructions 
CP 1242-7 
Operating Instructions, 03/2012, C79000-G8976-C247-03 
55
 
DONE  ERROR  STATUS 
Meaning 
80F4
H
 
Connection endpoint cannot be generated: 
Repeat the call. If necessary, check the connection parameters. 
80F6
H
 
Format error of a parameter in the called data block (wrong length, wrong format or 
invalid value) 
Check the configuration of the "TC_CON..." SDT. 
5.4.2 
TC_DISCON: Terminate connection via the GSM network 
Meaning 
The TC_DISCON instruction on an S7-1200 with CP 1242-7 terminates an ISO-ON-TCP, 
UDP, SMS or telecontrol connection that was established with the TC_CON instruction. 
You will find detailed information on the connection types in the description of the TC_CON 
instruction. 
TC_DISCON terminates the connection to the telecontrol server only logically. If you want 
the connection to the telecontrol server to be terminated physically, configure the connection 
as a "Temporary connection" in the "telecontrol server" parameter group in STEP 7. 
At the TCP/IP level, the connection is retained. Temporary stations terminate the connection 
automatically after sending the data. 
The ID parameter references the GPRS connection. The ID must be unique within the CPU 
and the same as the ID used with TC_CON. 
The INTERFACE parameter references the GPRS interface of the required local CP. The 
value must be the same as that used by TC_CON for INTERFACE. 
Call interface in FBD representation 
7&B',6&21
&211B28&
%22/
+:B,17(5)$&(
'21(
,'
,17(5)$&(
5(4
67$786
(5525
%86<
%22/
:25'
%22/
%22/