Siemens 6GK7242-7KX30-0XE0 사용자 설명서

다운로드
페이지 108
 
Configuration and programming 
 
5.4 Programming the telecontrol instructions 
CP 1242-7 
Operating Instructions, 03/2012, C79000-G8976-C247-03 
73
 
General parameters of the parameter fields 
Each field has the following general parameters: 
●  Id 
This parameter identifies the field and must not be modified. 
●  Length 
This parameter indicates the length of the field. The value serves as information. 
Fields with strings and / or arrays have a variable length. Due to hidden bytes, the actual 
length of fields can be greater than the sum of the displayed parameters. 
●  Mode 
The following values are permitted to these parameters: 
Table 5- 6 
Values of "Mode" 
Value 
Meaning 
Permanent validity of the configuration data 
Not relevant for the CP 1242-7 
Temporary validity of the configuration data, including deleting of existing permanent 
configuration data 
The permanent configuration data is replaced by the parameter fields of IF_CONF. 
Field for the parameter area "GPRS access" 
Table 5- 7 
IF_CONF_APN 
Parameter 
Data type 
Initial value 
Description 
Id 
UINT 
ID of the parameter field 
Length 
UINT 
 
Length of the parameter field in bytes: 174 
Mode 
UINT 
 
Validity (1: permanent, 2: temporary) 
AccesspointGPRS 
STRING [98] 
 
APN: Name of the access point of the GSM network 
provider to the Internet 
AccesspointUser 
STRING [42] 
 
APN user name 
AccesspointPassword  STRING [22] 
 
APN password 
Field for the parameter area "CP identification" 
Table 5- 8 
IF_CONF_Login 
Parameter 
Data type 
Initial value 
Description 
Id 
UINT 
ID of the parameter field 
Length 
UINT 
 
Length of the parameter field in bytes: 54 
Mode 
UINT 
 
Validity (1: permanent, 2: temporary)