Removal and replacement procedures  19 
Electrical 
Busway drop box 
The internal electrical busways provide a location to connect each of the drop boxes, which then power the 
PDUs. Stagger the drop boxes on the electrical busways by connecting one drop box to busway #1 and 
connecting the next drop box to busway #2. A staggered configuration enables load balancing with the rack 
equipment and is necessary to ensure redundancy. 
 
  
 
IMPORTANT:
  HP recommends that you shut down the associated IT equipment and de-energize 
the appropriate section of the power busway before attempting to remove or replace a busway 
drop box. The corresponding branch circuit breaker is labeled on the busway. 
  
You need a socket wrench to remove and replace the busway drop box. 
 
Removing the busway drop box 
1. 
Turn the power off by opening both breakers on the busway drop box (1).