HP Performance Optimized Data Center (POD) 20cp 서비스 매뉴얼

다운로드
페이지 81
 
Removal and replacement procedures  39 
5. 
Replace the four screws that secure the sensor cover (4). 
 
 
Chilled water system temperature sensor 
The HP POD 20c contains two chilled water header temperature sensors. One is located in the chilled water 
supply header and one is located in the chilled water return header. 
HP highly recommends replacing sensor internal components before replacing the entire sensor. For more 
information, see replacing the entire sensor. 
You need a wrench and a screwdriver to remove and replace the sensor. 
 
Removing temperature sensor from the chilled water system 
1. 
Identify the location of the sensor to be replaced, and then remove enough header insulation to uncover 
the sensor. 
2. 
Remove the sensor cover. 
3. 
Label and disconnect the sensor wiring.