HP Performance Optimized Data Center (POD) 20cp 참조 가이드
Supported facility connections 16
Supported facility connections
Environmental control system
The ECS developed for the HP water-cooled POD is a stand-alone control system that requires no external
connections with an external site system, BMS, public or private Internet sites, cloud, or wireless system to
connections with an external site system, BMS, public or private Internet sites, cloud, or wireless system to
properly control the POD operation.
The ECS includes Modbus TCP/IP connections through which a variety of data can be retrieved. These
The ECS includes Modbus TCP/IP connections through which a variety of data can be retrieved. These
capabilities enable you to connect, at your expense, with the stand-alone ECS system to monitor the
operating parameters of the POD. It is your responsibility (or your representative's or agent's responsibility)
operating parameters of the POD. It is your responsibility (or your representative's or agent's responsibility)
to integrate this communication capability into any existing BMS or monitoring system.
CAUTION:
To ensure that alarm conditions can be identified and resolved, HP recommends that
you remotely monitor all alarm conditions. Failure to monitor the alarm conditions can cause
delays in appropriate action during an alarm condition.
Additional POD connections
The HP POD 20c provides various connection points to your facility. It is your responsibility to facilitate these
connections. HP can make these connections when specifically contracted to deliver these services and a
connections. HP can make these connections when specifically contracted to deliver these services and a
Scope of Work has been drafted, reviewed, and signed for delivery services. Available POD connections
include the following:
•
Life safety systems
o
EPO
o
Fire detection
o
Fire suppression
•
Site communication
o
Phone
o
Access control
•
Networking—IT connections
Connection portals
Networking and connection portals are located on the cargo end of the HP POD 20c. Each HP POD 20c has
six 6.35-cm (2.5-in) portals for customer data connection. These portals are provided to allow the customer
six 6.35-cm (2.5-in) portals for customer data connection. These portals are provided to allow the customer
to make connections to the HP POD 20c.