HP Performance Optimized Data Center (POD) 20cp 참조 가이드

다운로드
페이지 37
 
Appendix C: Regulatory compliance notices  31 
Appendix C: Regulatory compliance notices 
HP POD 20c regulatory compliance 
The HP POD 20c complies with the following regulatory standards. 
  
Standard  Certification level 
Standard title 
UL 60950  ETL "Listed" 
 
UL 60950—Standard for Safety Information Technology 
Equipment, Part 1: General Requirements, Issue: 2007/03/27, 
Edition: 2 
 
UL 60950—Standard for Safety Information Technology 
Equipment, Part 22: Equipment to be Installed Outdoors, Issue: 
2007/04/23, Edition: 1 
NFPA 70 
ETL "Classified" 
NFPA 70—National Electric Code, 2008 Edition, © 2008 National 
Fire Protection Association 
NFPA 72 
Designed to Comply 
With applicable 
requirements 
National Fire Alarm code, 2007 Edition, © 2006 National Fire 
Protection Association 
NFPA 2001  Designed to Comply 
With applicable 
requirements 
NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems, 
2008 Edition, © 2008 National Fire Protection Association 
IBC 2009 
Designed to Comply 
With applicable 
requirements 
2009 International Building Code, © 2010 International Code 
Council, Inc. 
 
 
Safety and NEC compliance 
The HP POD 20c is certified to UL 69050-1/IEC 60950-22 as an Information Technology Product and 
classified according to the National Electric Code NFPA 70. For more information, see "HP POD 20c 
regulatory compliance (on page 
)." 
The HP POD 20c is not suitable for long-term human occupancy. The HP POD 20c is Listed as a Product that 
provides service access areas for periodic maintenance and service. These areas must be used only by 
owner-authorized and qualified personnel who are trained in the maintenance and service of the HP POD 
20c components. 
  
 
IMPORTANT:
  Before installing the HP POD 20c, consult your local AHJ for applicable 
regulations and to review site-specific location guidelines. If needed, obtain any necessary 
permits. 
  
Additional considerations for safety and NEC compliance are as follows: 
 
The HP POD 20c is listed as an Information Technology Product to UL 60950. 
 
The HP POD 20c is evaluated as a "non-inhabitable product" that provides "service access" areas for 
customer-authorized, qualified, and trained service personnel. 
 
The electrical connections of the HP POD 20c are evaluated as feeder connections for connection to an 
existing facility, and are not suitable as "service entrance" for connection to the utility.