HP POD specifications  14 
Item 
Component 
Fan sequencers 
Fan power relays 
Redundant power relays 
10 
EPO controls and indicators 
 
 
Water supply specifications 
Feature 
Specification 
Facility input temperature to HP POD 
12º to 24ºC (55º to 75ºF) 
Working pressure 
1034 kPa (150 psi) 
HP POD pressure drop 
1732 kPa (25 psi) 
HP POD water flow rate 
454 l/min (120 gal/min) 
Cooling water supply and return 
connections 
North America: 
Two 7.62 cm (3 in.) ASME 
B16.5 class 150# flanges 
International: 
Two DIN PN16 DN80 flanges 
Humidifier 
See the humidifier manual for 
exact requirements