Removal and replacement procedures  15 
Removal and replacement procedures 
Safety considerations 
The HP POD 40c G2 is listed to the UL 69050 standard as an Information Technology Product and Classified 
according to the NEC, NFPA-70, 2008. 
The HP POD 40c G2 is not suitable for long term personnel occupancy. 
The safety information is specific to the people operating and maintaining the components of the HP POD 
40c G2. 
  
 
IMPORTANT:
  All plumbing to and from the HP POD 40c G2 must be completed by a licensed 
plumber. 
  
  
 
IMPORTANT:
  All wiring in and around the HP POD 40c G2 must be completed by a licensed 
electrician. 
  
 
Operator safety 
The HP POD 40c G2 provides service access areas for periodic maintenance and service and is only to be 
used by owner-authorized personnel specifically trained in the maintenance and service of the HP POD 40c 
G2. 
The HP POD 40c G2 is not a habitable structure suitable for long term personnel occupancy. 
  
 
WARNING:
  To avoid the risk of personal injury or loss of life, all personnel must comply with PPE 
requirements when opening or working inside areas of the HP POD 40c G2 that are marked as 
hazardous voltage, per NFPA 70E in accordance with NEC (NA) and IEC (EMEA and APJ). 
  
  
 
WARNING:
  To avoid the risk of personal injury, hearing protection must be worn at all times 
when working inside the HP POD 40c G2. 
  
  
 
WARNING:
  To avoid the risk of personal injury or damage to the equipment, do not insert 
anything inside the electrical busways except the approved HP busway drop boxes.   
  
The customer is responsible for completing any Environmental Health and Safety (EHS) evaluation of the HP 
POD 40c G2 or any attached structural component purchased through HP. The customer must complete an 
arc flash assessment of the HP POD 40c G2 and the associated electrical supply system for operation, 
maintenance, and so on. 
 
Fire detection and suppression 
The fire suppression system, supplied as an optional component of the HP POD 40c G2, is a "Manufacturer 
Designed" system specifically for this HP product, in compliance with national standards.