HP Performance Optimized Data Center (POD) 40c 서비스 매뉴얼

다운로드
페이지 82
 
Periodic maintenance  64 
Component to be inspected 
Task 
Frequency 
Capable Party 
— 
Inspect for any water leaks and 
replace the cylinder if necessary. 
Inspect for blackened areas on the 
cylinder and, if present, check the 
condition of the electrodes. If 
necessary, replace the cylinder. 
Quarterly 
HP and certified 
facilities personnel 
— 
Replace the cylinder. 
Annually 
HP and certified 
facilities personnel 
 
 
Leak detection maintenance 
  
 
WARNING:
  To reduce the risk of electric shock or damage to the equipment, use extreme 
caution when removing and replacing components that involve water around the electrical 
equipment. There is great risk of electrical shock when water is used near electricity. 
  
  
 
CAUTION: 
 If a serious leak develops, shut down the POD immediately and isolate the chilled 
water cooling system from the site. Contact HP immediately to initiate a field service call. Do not 
attempt to repair the chilled water cooling system. Attempting to self-repair the chilled water 
cooling system during the warranty or service contract period shifts all liability to you. 
  
  
 
IMPORTANT:
  HP recommends shutting down the POD after a leak is detected. For more 
information, see "Power down procedure" in the user guide. 
  
Non-isolable leak detection 
A non-isolable leak is a leak from the main supply line or the return header. 
To repair a non-isolable leak: 
1. 
Power down all IT equipment. 
2. 
Re-direct the leaking water away from the IT equipment. 
3. 
Repair the leak or contact HP if you are still within your service contract. 
Isolable leak detection 
An isolable leak is any type of leak that does not occur from the main supply line or the return header. 
To repair an isolable leak: 
1. 
Inspect the zone indicated on the ECS Status Overview screen. You might need to inspect each zone 
condensate drain pan to determine the exact location of the leak. 
2. 
Power down the IT equipment in the zone where the leak is located. 
3. 
Determine the affected heat exchanger. 
4. 
Close and danger tag the supply and return valves to the affected heat exchanger. 
If the heat affected exchanger cannot be identified, close all the heat exchanger supply and return 
valves in the affected zone and open one supply valve at a time to determine the location of the leak. 
5. 
Repair the leak or contact HP if you are still within your service contract.