HP Performance Optimized Data Center (POD) 40cp 설치 가이드

다운로드
페이지 21
 
HP POD specifications  11 
External hot aisle view 
 
 
Water supply specifications 
 
Feature 
Specification 
Facility input temperature to HP POD 
12º to 24ºC (55º to 75ºF) 
Working pressure 
1034 kPa (150 psi) 
HP POD pressure drop 
1732 kPa (25 psi) 
HP POD water flow rate 
908.5 l/min (240 gal/min) 
Cooling water supply and return 
connections 
Two 10.16 cm (4 in) 
ANSI/ASME 150# flanges 
Humidifier 
See the humidifier manual for 
exact humidifier requirements