HP Performance Optimized Data Center (POD) 40cp 설치 가이드
HP POD specifications 11
External hot aisle view
Water supply specifications
Feature
Specification
Facility input temperature to HP POD
12º to 24ºC (55º to 75ºF)
Working pressure
1034 kPa (150 psi)
HP POD pressure drop
1732 kPa (25 psi)
HP POD water flow rate
908.5 l/min (240 gal/min)
Cooling water supply and return
connections
connections
Two 10.16 cm (4 in)
ANSI/ASME 150# flanges
ANSI/ASME 150# flanges
Humidifier
See the humidifier manual for
exact humidifier requirements
exact humidifier requirements