EXCEL 500/600 INSTALLATION INSTRUCTIONS 
Battery Activation during Commissioning
(XC6010, only) 
The controller is delivered from the factory with the battery in 
the computer module electrically isolated from the internal 
circuitry by a safety tag to prevent the battery from 
discharging in transit. 
The controller is delivered from the factory with the battery in 
the computer module electrically isolated from the internal 
circuitry by a safety tag to prevent the battery from 
discharging in transit. 
1.   Unscrew the computer module cover with a  
screwdriver.  
Fig. 37. Accessing the battery compartment 
Fig. 38. Removing the faceplate 
Fig. 39. Battery compartment 
2.   Remove the safety tag. 
3.   Install the cover. 
Replacing the Battery 
IMPORTANT 
Batteries must not be disposed of as household 
waste. The law requires that you as the consumer 
return the waste batteries. Dispose of the battery 
according to legal regulations 
During normal operation, the battery is periodically tested 
under load. If the battery voltage falls below a threshold of 
2.45 V during operation or under load, the computer module 
generates an error message which is displayed on the MMI 
as a system alarm. The battery must be replaced as soon as 
possible after the system alarm. 
IMPORTANT 
The line power supply must not be interrupted while 
replacing the battery; otherwise, all data held in RAM 
is lost. 
NOTE:   In the event that your fingers touch the battery 
contacts, please clean the contacts with cleaning 
agent. 
1.   Unscrew the computer module cover with a screwdriver 
as shown in the previous section. 
2.   Release the latch holding the battery in its compartment 
3.   Remove the old battery. 
4.   Insert the new battery with the positive contact pointing 
upwards. 
Battery type: 
Lithium battery 3 V, 1000 mAh, e.g. VARTA lithium battery 
CR1/2 AA – 3 V, 1000 mAh 