Honeywell Excell 500/600 Controll System 500-XCL5010 사용자 설명서

다운로드
페이지 48
EXCEL 500/600 INSTALLATION INSTRUCTIONS 
ELECTRICAL CONNECTIONS 
When connecting the controller, both VDE, National Electric 
Code NEC (or equivalent) and any local regulations con­
cerning grounding and zero voltage must be observed. 
Electrical work should be carried out by a qualified electrician. 
Under no circumstances should spare controller terminals be 
used as wiring support points. Doing so could damage the 
modules. 
The electrical connections must be made at the terminal 
blocks. The corresponding connection diagrams are on the 
individual modules.
 WARNING 
Switch power OFF before making connections to or 
removing connections from terminals to avoid 
electrical shock or equipment damage. 
IMPORTANT (FOR EUROPE, ONLY) 
To comply with CE requirements, devices with a 
voltage in the range of 50...1000 Vac or 
75...1500 Vdc which are not provided with a supply 
cord and a plug or with other means for 
disconnection from the supply having a contact 
separation of at least 3 mm in all poles, must have 
the means for disconnection incorporated in the 
fixed wiring. 
Cable Routing 
The minimum distance to power mains cables is 0.4 in. (10 
mm) for shielded cable and 4 in. (10 cm) for unshielded cable. 
All low-voltage signal and output cables should be regarded 
as communication circuits in accordance with VDE 0100 and 
VDE 0800 (or NEC or other equivalent), and should therefore 
be routed separately from mains cables. 
Joining sensor cables should be avoided. 
Shielding Input / Output Module and Power
Supply Cables 
Shielding input and output module and power supply cables 
is not necessary if the general guidelines for cable routing are 
observed. If, in certain cases, the routing guidelines cannot 
be observed, then shielded cable must be used. 
The shield must not be terminated at a controller; instead, to 
avoid ground loops, the shield must be grounded (at only one 
end) at the control panel. 
To prevent ground loops, shielding of input/output cables 
leading to peripheral devices must be grounded only at the 
control panel end. 
Shielding of Data-Transmitting Cables 
Connect the shield of the system bus (C-Bus) to system 
ground on both ends. Each end of the shield on the system 
bus should be connected to the system ground terminal of the 
respective computer module. Do not connect it to the control 
panel earth or any other earth ground points. 
NOTE:   The L
ON
W
ORKS
 bus must not be shielded on the 
CPU side. 
To connect remote operator interface units, ready-made 
cables are available (XW565; XW582, XW583, etc.) with the 
shield already connected to the computer module plug end. 
Grounding (XC5010C / XC6010, only) 
The controller should be grounded using as short a cable as 
possible (minimum 16 AWG [1.5 mm²]) between the control 
panel and the terminal block of the power supply module. 
System Ground 
WARNING 
High voltage 
Risk of electrical shock or equipment damage. 
The controller's system ground must have no 
connection with the control cabinet ground! 
NOTE:   A document providing additional information on 
system grounding (if required) is available via the 
Honeywell Technical Assistance Center (TAC) or, for 
Honeywell employees, on the Docu Server under: 
http://web.ge51.honeywell.de/dep/mc/TAC_Tips
RFI Suppression 
Honeywell actuators are RFI (Radio Frequency Interference) 
suppressed as standard in accordance with VDE 0871/B and 
VDE 0875/N. 
EN1R-1047GE51 R0902  
20