HP Performance Optimized Data Center (POD) 20cp 빠른 설정 가이드

다운로드
페이지 38
 
Site requirements  12 
Front view shown 
 
 
Utilities 
Consider the proximity to required utilities, such as power, water, and network connections. While the 
required utilities can be brought to nearly any selected site, there is the potential for increased costs and 
decreased efficiency when the HP POD 20c is located farther from the utility sources. 
For utility clearance information, see "Dimensions and clearances (on page 
).
 
Humidifier water supply 
The HP POD 20c requires supply water for the humidifier. The supply water must meet the following 
requirements. 
 
Requirement   
Specification 
Pressure 
Between 20 and 110 psi, 0.1 and 0.8 MPa 
Temperature 
Between 1º and 40°C (33º and 104°F) 
Minimum flow rate 
1.45 lpm (0.12 gpm) 
Connection 
1.9 cm (.75 in) G 
Adapter to 1.9 cm (.75 in) FPS 
Hardness 
No greater than 40°fH (equal to 400 ppm of CaCO
3
Conductivity 
100 to 1250 μS/cm 
Organic compounds 
None 
Type of water 
Drinking water. Do not use de-mineralized or softened water. 
Instant water fill flow 
rate 
0.6 lpm (0.16 gpm) 
Humidifier 
For the exact requirements, see the humidifier documentation. 
   
 
IMPORTANT:
  If your water is out of range, consult a water quality expert. 
In addition to the previous requirements, observe the following requirements and recommendations: