Outback Power Systems Automatic Generator Start 전단

다운로드
페이지 2
•  DC Genset. Normally, the FX inverter requires AC input to make certain the generator started. If you need to use a
DC generator instead, you can tell the AGS not to look for AC input. AGS stops the generator when the DC voltage
rises to a certain value.  (This does not guarantee good battery charging.  Also, the AGS has to take it on faith that the 
generator has even started.)
You do not have to select one function over another — the AGS can start the generator for any reason. If you don’t know 
why the generator started, a MATE menu can tell you.   
Starting Functions:  Battery SOC
The  OutBack  FlexNet  DC  sends  battery  state-of-charge  (“SOC”)  information  to  the  MATE’s
AGS menus. If the FlexNet DC is present, AGS can also be programmed to start and stop the
generator based on specified levels of charge. SOC is the most accurate AGS function if you are 
concerned about battery care. 
Without the MATE
The AGS functions, including SOC, are based in the MATE itself and are programmed in the MATE’s own menu area. If the 
MATE cannot be installed or must be removed for some reason, AGS cannot be used.  
The OutBack FX inverter has a function of its own called GenAlert.  GenAlert will energize the 
AUX output upon reaching low battery voltage for a certain amount of time, and will turn off 
the output after reaching a high voltage for a certain time (all settable). This can allow the 
inverter to automatically start the generator, even if there is no MATE.  (However, this may not 
allow the full charge cycle.) The MATE must still be used for the initial setup, in the FX section 
of the menus.
The  OutBack  FlexNet  DC  has  an  AUX  switch  of  its  own. This  is  a  set  of  dry  contacts,  instead  of  a  12-volt  output. The
FlexNet’s AUX switch can perform automatic start if the 2-wire controls are connected directly to it, and it can do so based 
on SOC, from the FlexNet’s own readings. (With no MATE, the other AGS functions are still unavailable.  Unlike the MATE, 
the FlexNet’s SOC feature cannot be used on the FX Aux output.) The MATE must still be used for the initial setup, in the 
DC section of the menus.
AGS and AUX Selection
AGS can only send commands to one AUX at a time.  You can connect the 2-wire control to one FX inverter in a multi-unit 
system, and then direct the AGS commands there.  All the above functions will be active on that unit, although not on any 
of the other FX inverters. (This will cancel GenAlert or other AUX function programmed into that inverter.)  Similarly, AGS 
can be directed to the FlexNet’s AUX switch instead, with all AGS functions being active there (although the FlexNet’s own 
function is not cancelled). You cannot send AGS commands to the AUX of any OutBack charge controller.
Stopping
The AUX removes its output to stop the generator, whether operating by AGS, GenAlert, FlexNet DC. A two-wire-start
generator  will  stop  as  soon  as  the  wires  are  disconnected.  Along  with  automatic  shutoff,  the  generator  can  also  be 
stopped manually, if the FX fails to see the proper input, or if another error occurs.
AGS  can  perform  generator  cooldown.  It  will  disengage  the  inverter  from  the  generator  for  a  selectable  time  before 
sending  the  stop  command,  to  keep  the  generator  from  stopping  while  under  load.  Similarly,  AGS  can  also  perform 
generator warmup, while starting. These functions are only present for AGS.