White Rodgers 50M56-743 Direct Replacement Furnace Control for Goodman Multi Speed Nitride Ignition Integrated Furnace Control 설치 설명서

다운로드
페이지 8
50M56-743
Integrated Single or Two-Stage
HSI Integrated Furnace Control Kit
INSTALLATION INSTRUCTIONS
 
 DESCRIPTION
The 50M56-743 kit is an automatic gas HSI Integrated Furnace 
Control that employs a microprocessor to continually monitor, 
analyze, and control the proper operation of the gas burner, 
inducer, and fan.
Signals interpreted during continual surveillance of the 
thermostat and flame sensing element initiate automatic 
ignition of the burner, sensing of the flame, and system shut-
off during normal operation.
These controls incorporate system fault analysis for quick gas 
flow shut-off, coupled with automatic ignition retry upon sensing 
a fault correction.
Installation should be done by a qualified heating and air 
conditioning contractor or licensed electrician.
If in doubt about whether your wiring is millivolt, line, or low 
voltage, have it inspected by a qualified heating and air 
conditioning contractor or licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes 
and ordinances.
This control is a precision instrument, and should be handled 
carefully. Rough handling or distorting components could 
cause the control to malfunction.
Following installation or replacement, follow manufacturer’s 
recommended installation/service instructions to ensure 
proper operation.
 
 PRECAUTIONS
CAUTION
!
Do not short out terminals on gas valve or primary 
control. Short or incorrect wiring may damage the 
thermostat.
Failure to comply with the following warnings could result 
in personal injury or property damage.
FIRE HAZARD
•  Do not exceed the specified voltage.
•  Replace existing control with exact model and
dash number.
•  Protect the control from direct contact with water
(dripping, spraying, rain, etc.).
•  If the control has been in direct contact with
water, replace the control.
•  Label all wires before disconnection when
servicing controls. Wiring errors can cause 
improper and dangerous operation.
•  Route and secure wiring away from flame.
SHOCK HAZARD
•  Disconnect electric power before servicing.
•  Ensure proper earth grounding of appliance.
•  Ensure proper connection of line neutral and line
hot wires.
EXPLOSION HAZARD
•  Shut off main gas to appliance until installation
is complete.
WARNING
!
CONTENTS
Description ................................................................... 1
Precautions .................................................................. 1
Specifications .............................................................. 2
Installation ................................................................... 3
           Mounting & Wiring
Operation ..................................................................... 6
System Lockout and Diagnostic Features ................... 7
Troubleshooting ........................................................... 8
www.white-rodgers.com
www.emersonclimate.com
PART NO. 37-7474B
Replaces 37-7474A
1416
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE 
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL 
INJURY AND/OR PROPERTY DAMAGE.
50M56-743 Cross Reference Information
Goodman
White-Rodgers 
0130F00006
PCBBF122
50M56 289
0130F00006S
PCBBF122S
PCB00109
PCBBF132
PCBBF109
PCBBF132S