White Rodgers 21V51U-843 Universal Two-stage HSI Integrated Furnace Control Kit 설치 설명서

다운로드
페이지 8
TRI-COLOR (DSI LED) DIAGNOSTIC TABLE
Green 
LED 
Flash
Amber
LED 
Flash
Red LED
Flash
Error/Condition
Comments/Troubleshooting
1
Flame sensed when no flame should 
be present
Verify the gas valve is operating and shutting down properly. Flame 
in burner assemble should extinguish promptly at the end of the 
cycle. Check orifices and gas pressure.
2
Pressure switch stuck closed/ inducer 
error
Pressure switch stuck closed. Check switch function, verify inducer 
is turning off.
3
1st-stage pressure switch stuck open/
inducer error
Check pressure switch function and tubing. Verify inducer is turning 
on the pulling sufficient vacuum to engage switch.
4
Open limit switch
Verify continuity through rollout switch circuit.
5
Open rollout/open fuse detect
Verify continuity through rollout switch circuit, check fuse.
6
1st-stage pressure switch cycle 
lockout
If the first stage pressure switch cycles 5 times (open, closed) 
during one call for heat from the thermostat the control will lockout. 
Check pressure switch for fluttering, inconsistent closure or poor 
vacuum pressure.
7
External lockout (retries exceeded)
Failure to sense flame is often caused by carbon deposits on the 
flame sensor, a disconnected or shorted flame sensor lead or a 
poorly grounded furnace. Carbon deposits can be cleaned with 
emery cloth. Verify sensor is not contacting the burner and is located 
in a good position to sense flame. Check sensor lead for shorting 
and verify furnace is grounded properly.
8
External lockout (ignition recycles 
exceeded where flame is established 
and then lost)
Check items for exceeded retries listed above and verify valve is not 
dropping out allowing flame to be established and then lost.
9
Grounding or Reversed polarity
Verify the control and furnace are properly grounded. Check and 
reverse polarity (primary) if incorrect.
10
Module gas valve contacts energized 
with no call for heat
Verify valve is not receiving voltage from a short. If a valve wiring is 
correct and condition persists, replace module.
11
Limit switch open – possible blower 
failure overheating limit
Possible blower failure, restricted air flow through appliance or 
duct work. Verify continuity through limit switch circuit and correct 
overheating cause.
12
Module Ignitor contact failure
Fault code indicates the module ignitor contacts are not functioning 
properly. Replace module.
Solid
Module - internal fault condition
Module contacts for gas valve not operating or processor fault. 
Reset control. if condition persists replace module.
3 double 2nd-stage Pressure Switch Stuck 
Open/Inducer Error
Check pressure switch function and tubing. Verify inducer is turning 
on and pulling sufficient vacuum to engage switch.
1
Normal Operation with call for first 
stage heat
Normal operation - first stage
2
Normal Operation with call for second 
stage heat
Normal operation - first stage
3
W2 present with no W1
Second stage call for heat on thermostat circuit with no call for first 
stage. Verify  DIP switches are set for two stage thermostat and 
check thermostat first stage circuit. Configured for a multi-stage 
thermostat the Module will not initiate heating unless first stage call 
from thermostat is received.
4
Y present with no G call
Module will allow cooling to operate with only a "Y signal from 
the thermostat but will also trigger this code. Verify thermostat is 
energizing both "Y" and "G" on call for cool. Check "G" terminal 
connections.
Rapid
Low flame sense current
Low flame sense current is often caused by carbon deposits on 
the flame sensor, a poorly grounded furnace or a mis-aligned 
flame sense probe. Carbon deposits can be cleaned with emery 
cloth. Check for improve furnace and module ground. Verify sensor 
is located in or very near flame as specified by the appliance 
manufacturer.
1
Standby or Call for Cool
Normal operation. Waiting for call from thermostat or receiving 
thermostat call for cool.
www.white-rodgers.com
www.emersonclimate.com
White-Rodgers is a division 
of Emerson Electric Co.
The Emerson logo is a  
trademark and service mark 
of Emerson Electric Co.