Liebert MR1 사용자 설명서

다운로드
페이지 19
 
Section 3:  HARDWARE CONFIGURATION 
 
DIP Switch Settings  
The following user selectable operations are set by DIP SW1 on 
the display panel circuit board:  Refer to Table 2 and Figure 3. 
Position 
OFF 
ON 
1 Audible 
beeper 
enabled 
Audible beeper 
disabled 
2 Remote 
on/off 
disabled.  On/off 
button affects MR1 
operation only 
Remote on/off of 
Env. unit enabled.  
Env. unit must have 
remote on/off 
capability, or MR1 
will not be able to 
perform this function 
Optional alarm inputs 
disabled 
4 optional alarm 
inputs enabled 
4 Common 
alarm 
follows alarm 
condition 
Common alarm 
de-energized when 
alarm is silenced 
Table 2: DIP Switch Settings 
Note that factory default is OFF for all four positions. 
 
 
 
Liebert MR1 
 7