Part I - Venting Specifications for: 
 
48 Gallon, 65,000 BTU input (181.7 L, 19.1 kW/Hr) 
 
65 Gallon, 65,000 BTU input (246.1 L, 19.1 kW/Hr) 
 
75 Gallon, 76,000 BTU input (283.9 L, 22.3 kW/Hr)  
 
This water heater is a power vented appliance and is designed to vent its 
products of combustion through 3” (7.6 cm) or 4” (10.2 cm) diameter Schedule 40 
(solid or cellular core) PVC pipe to the outdoors.   This water heater may be 
either vented through the wall or vertically through the roof.  Use a 3” (7.6 cm) to 
4” (10.2 cm) reducer to connect to the vent outlet when using 4” (10.2 cm) PVC.  
Apply PVC cement at PVC locations. Table 2 lists the maximum vent lengths for 
this water heater using 3” (7.6 cm) PVC.  If possible, locate the water heater so 
that the venting length and number of elbows are kept to the minimum distance 
necessary to reach the outside.  If the installation requires venting lengths that 
exceed the lengths listed for 3” (7.6 cm) PVC in Table 2, then use 4” (10.2 cm) 
PVC for the vent connector.  Table 3 lists the venting distances allowed with 4” 
(10.2 cm) diameter PVC pipe.  When venting with 4” (10.2 cm) PVC, use a 4” 
(10.2 cm) to 3” (7.6 cm) reducer to exit through the building wall with 3” (7.6 cm) 
PVC.  Use the 3” (7.6 cm) vent terminal supplied with the water heater to 
terminate on the outside of the building.  If the length of 3” (7.6 cm) PVC needed 
to go through the wall is greater than 14” (35.5 cm), use 4” (10.2 cm) to go 
through the wall and reduce to 3” (7.6 cm) PVC immediately after exiting the 
outside wall.  Refer to the venting illustrations on the following pages.  Make sure 
the vent pipe terminal elbow fitting is at least 1” (2.5 cm) away from the edge of 
the wall. 
 
TABLE 2 - VENT CONNECTOR LENGTHS 
FOR 3” (7.6 cm) DIAMETER PVC
 
Terminating
 
# of 90
° Elbows 
(excluding vent 
terminal)
 
Maximum 
Length
 
Minimum 
Length
 
Through the Wall 
40 ft (12.2 m) 
2 ft (.6 m) 
Through the Wall 
35 ft (10.7 m) 
3 ft (.9 m) 
Through the Wall 
30 ft (9.1 m) 
5 ft (1.5 m) 
Through the Wall 
25 ft (7.6 m) 
8 ft (2.4 m) 
Through the Roof 
40 ft (12.2 m) 
2 ft (.6 m) 
Through the Roof 
35 ft (10.7 m) 
3 ft (.9 m) 
Through the Roof 
30 ft (9.1 m) 
5 ft (1.5 m) 
Through the Roof 
25 ft (7.6 m) 
8 ft (2.4 m) 
 
 
 
Venting (Part I) continued- 
 