White Rodgers 24A34-1 Electric Heat Sequencer 설치 설명서

다운로드
페이지 4
24A34 Series
Fan/Heat Sequencers
INSTALLATION INSTRUCTIONS
 
 DESCRIPTION
 
 SPECIFICATIONS
The 24A34 Series Fan/Heat Sequencer gives the service tech-
nician a direct replacement for sequencing both fan and heat.  
The terminal markings on the 24A34 sequencers are equivalent 
to most other manufacturers’ types.
These sequencers may be wired in series, as shown in wiring 
diagrams, to allow sequencing of one through seven element 
furnaces.
CAUTION
!
To prevent electrical shock and/or equipment damage, 
disconnect electric power to system, at main fuse or 
circuit breaker box, until installation is complete.
Do  not  use  on  circuits  exceeding  specified  voltage.   
Higher  voltage  will  damage  control  and  could  cause 
shock or fire hazard.
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE 
INSTALLING  OR  OPERATING THIS  CONTROL  COULD  CAUSE  PERSONAL 
INJURY AND/OR PROPERTY DAMAGE.
www.white-rodgers.com
www.emersonclimate.com
PART NO. 37-4800C
Replaces 37-4800B
1050
TABLE NOTES:
 M1-M2 and M3-M4 are always first switches to turn ON and last to turn OFF. All other switches are random ON and random OFF
 24A34-14 Switch contacts designated F
-  F
2
 instead of M
- M
2
  These contacts switch simultaneously
NOTE: Underwriters Laboratories requires a fan interlock circuit to insure the blower remains operating whenever more than one sequencer is used. The fan in-
terlock should be the M
1
 / M
2
 contacts of the second or third sequencer. All M
1
 / M
2
 contacts are wired to the blower motor so that any sequencer that is energized 
will keep the blower ON.
Electrical Ratings - Single Load Contact Ratings (All Models)
VAC
Resistive (Non-Inductive)
Motor Ratings (Inductive)
Pilot Duty
Watts
Amps
Full Load
Locked Rotor
120
3000
25.0
14.0A
72.0A
125 VA
240
6000
25.0
7.0A
42.0A
125 VA
480
6000
12.5
480 VA
Electrical Ratings - Single Load Contact Ratings (All Models)
Model 
Number
Timings Switches
Timings 
– 
ON
Timings 
– 
OFF
M1-M2 M3-M4 M5-M6 M7-M8 M9-M10 M1-M2 M3-M4 M5-M6 M7-M8 M9-M10
24A34-1
1
1
1-20
40-110
24A34-2
1
1
30-90
1-30
24A34-3
 
1
2
1-20
1-20
40-110 40-110
24A34-4
1
2
30-90
30-90
1-30
1-30
24A34-5
 
2
3
1-110
1-110
1-110
1-110
1-110
1-110
  24A34-6
 
2
4
1-110
1-110
1-110
1-110
1-110
1-110
1-110
1-110
24A34-14 ➀➁
4
5
1-160
1-160
1-160
1-160
1-160
1-160
1-160
1-160 1-160
1-160
24A34-15
1
1
1-60
75-95