White Rodgers 50M56U-843 Universal Single Stage HSI Integrated Furnace Control Kit 설치 설명서

다운로드
페이지 8
PAGE 3 CONTAINS WIRING HARNESS AND 
BLOWER CONNECTION INSTRUCTIONS FOR 
ALL APPLICATIONS AND IMPORTANT OEM 
REPLACEMENT INSTRUCTION FOR:
● TRANE / AMERICAN STANDARD
● RHEEM / RUUD
 BRYANT / CARRIER / DAY & NIGHT / PAYNE
INSTALLER MUST READ
50M56U-843
Universal Single Stage
HSI Integrated Furnace Control Kit
INSTALLATION INSTRUCTIONS
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS 
CAREFULLY BEFORE INSTALLING OR OPERATING 
THIS CONTROL COULD CAUSE PERSONAL INJURY 
AND/OR PROPERTY DAMAGE.
 
 DESCRIPTION
The 50M56U-843 kit is a Universal Single Stage HSI Integrated 
Furnace Control that employs a microprocessor to continually 
monitor, analyze, and control the proper operation of the gas 
burner, inducer, and fan.
The kit contains:
•  50M56-843 Ignition Control Module
•  21D64-2 Ignitor Kit
•  Set of Interconnect Harnesses
Installation should be done by a qualified heating and air 
conditioning contractor or licensed electrician.
If in doubt about whether your wiring is millivolt, line, or low 
voltage, have it inspected by a qualified heating and air 
conditioning contractor or licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes 
and ordinances.
This control is a precision instrument, and should be handled 
carefully. Rough handling or distorting components could 
cause the control to malfunction.
Following installation or replacement, follow manufacturer’s 
recommended installation/service instructions to ensure 
proper operation.
 
 PRECAUTIONS
Do not short out terminals on gas valve or primary 
control. Short or incorrect wiring may damage the 
thermostat.
CAUTION
!
Failure to comply with the following warnings could result 
in personal injury or property damage.
FIRE HAZARD
•  Do not exceed the specified voltage.
•  Replace existing control with exact model and
dash number.
•  Protect the control from direct contact with water
(dripping, spraying, rain, etc.).
•  If the control has been in direct contact with
water, replace the control.
•  Label all wires before disconnection when
servicing controls. Wiring errors can cause 
improper and dangerous operation.
•  Route and secure wiring away from flame.
SHOCK HAZARD
•  Disconnect electric power before servicing.
•  Ensure proper earth grounding of appliance.
•  Ensure proper connection of line neutral and line
hot wires.
EXPLOSION HAZARD
•  Shut off main gas to appliance until installation
is complete.
WARNING
!
CONTENTS
Description ...................................................................  1
Precautions ..................................................................  1
Specifications ..............................................................  2
Installation ...................................................................  2
           Mounting & Wiring
Operation ..................................................................... 6
Troubleshooting ........................................................... 8