Dell™ PowerApp.web 100 and 
PowerApp.cache 100 Appliances 
Rack Installation Guide
This installation guide provides instructions for trained service technicians installing 
one or more Dell
 
PowerApp™ 100 appliances in a rack. This guide includes proce-
dures for the following three rack kits: 
Two-post center-mount 
Two-post flush-mount
Four-post rack cabinet
One rack kit is required for each PowerApp 100 system to be installed in the rack. 
Two-Post Center-Mount Rack Kit 
Installation
This procedure provides instructions for installing a Dell PowerApp 100 appliance in a 
two-post open-frame relay rack, such as those found in telecommunications equip-
ment facilities. Both 3-inch and 6-inch wide two-post racks are accommodated.
The two-post open-frame relay rack must be properly secured to the floor, to the ceil-
ing or upper wall, and where applicable, to adjacent racks, using floor and wall 
fasteners and bracing specified or approved by the rack manufacturer or by industry 
standards. Refer to the two-post open-frame relay rack manufacturer’s installation 
documentation for precautionary warnings and information before attempting this 
installation.
CAUTION: Do not attempt to install the PowerApp system into a two-post 
open-frame relay rack that has not been securely anchored in place. Dam-
age to the system and personal injury may result.
Refer to “Safety Instructions” at the front of this document for additional safety infor-
mation regarding rack installation.