Example PID Algorithm Listings   501
/* At startup in the Manual control mode, the output will be held at
*/
/* its current value.
*/
/*
*/
/* At startup, in the Automatic control mode, the output will slew
*/
/* from its initial value towards P_factor * Error at a rate determined
*/
/* by the Integral control constant (I_out is initialized to cancel P_out).
*/
/*
*/
/* For process monitoring, data may be sent to the FIFO and current 
*/
/* value table (CVT).  There are three levels of data logging, controlled
*/
/* by the History_mode variable.  The location in the CVT is based
*/
/* on 'n', where n is the algorithm number (as returned by ALG_NUM, for */
/* example).  The first value is placed in the (10 * n)th 32-bit word of
*/
/* the CVT.  The other values are written in subsequent locations.
*/
/*
*/
/*  History_mode = 0:  Summary to CVT only.  In this mode, four values */
/*    are output to the CVT.
*/
/*
*/
/*        Location      Value 
*/
/*            0         Input
*/
/*            1         Error
*/
/*            2         Output
*/
/*            3         Status
*/
/*
*/
/*  History_mode = 1:  Summary to CVT and FIFO.  In this mode, the four*/
/*    summary values are written to both the CVT and FIFO.  A header
*/
/*    tag (256 * n + 4) is sent to the FIFO first.
*/
/*
*/
/*  History_mode = 2:  All to FIFO and CVT.  In this mode, nine values
*/
/*    are output to both the CVT and FIFO.  A header tag (256 * n + 9)
*/
/*    is sent to the FIFO first.
*/
/*  
*/
/*        Location      Value
*/
/*            0         Input
*/
/*            1         Error
*/
/*            2         Output 
*/
/*            3         Status
*/
/*            4         Setpoint
*/
/*            5         Proportional term
*/
/*            6         Integral term
*/
/*            7         Derivative term
*/
/*            8         Setpoint Derivative term
*/
/* */
/********************************************************************************************/
/*
*/
/* User determined control parameters
*/
    static float Setpoint = 0; /* The setpoint
*/
    static float P_factor = 1; /* Proportional control constant
*/
    static float I_factor = 0; /* Integral control constant
*/
    static float D_factor = 0; /* Derivative control constant
*/
    static float Error_max = 9.9e+37; /* Error alarm limits
*/
    static float Error_min = -9.9e+37;
    static float PV_max = 9.9e+37; /* Process Variable alarm limits
*/
    static float PV_min = -9.9e+37;
    static float Out_max = 9.9e+37; /* Output clip limits
*/
    static float Out_min = -9.9e+37;
    static float D_max = 9.9e+37; /* Derivative clip limits
*/
    static float D_min = 9.9e+37;
    static float I_max = 9.9e+37; /* Integral clip limits
*/
    static float I_min = -9.9e+37;
    static float Man_state = 0; /* Activates manual control
*/
    static float Man_out = 0; /* Target Manual output value
*/
    static float Man_inc = 0; /* Manual outout change increment
*/
    static float SD_factor = 0; /* Setpoint Derivative constant
*/
    static float SD_max = 9.9e+37; /* Setpoint Derivative clip limits
*/
    static float SD_min = 9.9e+37;
    static float History_mode = 0; /* Activates fifo data logging
*/
/*
*/