Issued: 02/2008 
Operator Control with WinCC flexible 2005 
Preface Installation Project Description Step7 Project HMI Station WinCC flexible Project Messages Recipes User Management 
9 CONFIGURING 
MESSAGES 
 
The representation of the color mixing plant is by and large completed. What still needs to be done 
are the messages. Messages are generated if an event bit occurs (bit messages), or when a limit is 
overrange or underrange (analog messages). 
The message texts contain a description of the cause for the message with the message status, or 
only notes on the current operation of the plant. 
We differentiate message classes such as warnings or errors for operational messages and  fault 
messages. Operational messages refer to the states of a machine or a process.  Fault messages 
indicate alarms of a machine or a process and have to be acknowledged. 
 
9.1 Analog 
Messages 
 
The levels of the three tanks and of the container are to be monitored. 
If a tank or the container is full, a fault message is to be read out. 
 
In the project window, double click on analog messages. 
Enter the message texts and the monitored variables. 
For the tank limits, use the variable of the maximum fill setpoint. 
For the container limit, enter as the constant value  2999. 
 
 
 
Note 
You can also generate several messages for one monitored variable.  
You only have to set different limits with the rising or falling edge. 
 
9.2 Bit 
Messages 
 
Bit messages are configured just like analog messages; only here, the message is read out when an 
event bit is pending. 
 
 
 
Maximum level reached
Container full 
Error
  Error         CONTENT_T1
 At rising edge