Siemens Webcam TP177B 사용자 설명서
Automation and Drives - SCE
T I A Training Document
Page 17 of 129
Module
F6
Issued: 02/2008
Operator Control with WinCC flexible 2005
Preface Installation Project Description Step7 Projekt HMI Station WinCC flexible Project Messages Recipes User Management
4.2 Hardware
Configuration
Enter the hardware configuration of the controller you are using. Take note of the settings in the
sample configuration.
For our mixing plant, we are using the following hardware:
Slot 1: PS307 2A
sample configuration.
For our mixing plant, we are using the following hardware:
Slot 1: PS307 2A
6ES7 307-1BA00-0AA0
Slot 2: CPU 314C-2DP
6ES7 314-6CF00-0AB0
The CPU 314C-2DP is assigned the Profibus DP Addr.2 and is connected.
The CPU 314C-2DP is assigned the MPI Addr.2 and is connected.
The clock flag is set to MB100.
At the integrated inputs and outputs DI24/DO16, the inputs are set starting with Address 0, and the
outputs starting with Address 4.
Save and compile the hardware configuration.
Load the hardware to the PLC.
Close the hardware configuration.
Note
The SIMATIC S7 controller can also be simulated with the PLC simulator PLC SIM.
However, the simulator has to be started prior to loading the hardware to the CPU.