Operator Control with WinCC flexible 2005 
Preface Installation Project Description Step7 Project HMI Station WinCC flexible Project Messages Recipes User Management 
8.3.3 
Configuring the Manual Mode for the Outflow Valve of the Container 
 
We are creating an additional button for opening the outflow valve.  
From the tool window, under Basic Objects, drag a Button into the basic display. 
Under Allgemein (General), at Text  AUS, enter “Ablauf öffnen“ (open outflow). Set the check mark 
for Text EIN, and enter the text “Ablauf offen“ (outflow open). 
Caution! After entering the text, don’t press the enter key; otherwise, a new line is generated. 
 
Change the background color to white, and select a smaller font size. 
Set the position and the size. 
 
 
 
 
In the function list, select the function “SetzeBit“ at Drücken (press). 
 
 
 
 
From DB1, select as variable “hand_ablauf_behaelter“ (manual outflow container). 
We want to generate the function of a button; for that reason, we are now configuring the function 
RuecksetzeBit“ (reset bit) with the variable “hand_ablauf_behaelter“ when releasing the button.