Chapter 3 – Point Database 
24 
Siemens Industry, Inc. 
BACnet ATEC Owner's Manaul 
125-5050, Rev. AA 
 
4/20/2010 
Chapter 3 – Point Database 
Chapter 3 presents a description of the BACnet VAV Controller — Electronic Output 
point database, including point descriptors, point addresses, and a listing of 
applications in which each point is found. 
 
Descriptor 
Address
1
 
Application 
Description 
CTLR ADDRESS 
01 
All 
Identifies the controller on the FLN trunk. 
APPLICATION 
02 
All 
Identification number of the program running in the controller. 
RMTMP OFFSET 
03 
All 
Compensates for deviations between the value of ROOM 
TEMP and the actual room temperature. This corrected value 
is displayed in CTL TEMP. RMTMP OFFSET + ROOM TEMP 
= CTL TEMP 
ROOM TEMP 
{04}
2
 
All 
Actual reading from the room temperature sensor. 
HEAT.COOL 
{05} 
All 
except
 
2560, 2597  
Current mode of operation for applications that can be in 
either a heating mode or a cooling mode. 
DAY CLG STPT 
06 
All 
except
 2597 
The temperature setpoint in degrees that the controller 
maintains during day periods in cooling mode if a room 
temperature sensor setpoint dial is not present or is not used. 
See STPT DIAL. 
DAY HTG STPT 
07 
All 
except
 2560, 2597  The temperature setpoint in degrees that the controller 
maintains during day periods in heating mode if a room 
temperature sensor setpoint dial is not present or is not used. 
See STPT DIAL. 
NGT CLG STPT 
08 
All 
except
 2597  
The temperature setpoint in degrees that the controller 
maintains during the night periods in cooling mode. 
NGT HTG STPT 
09 
All 
except
 2560, 2597  The temperature setpoint in degrees that the controller 
maintains during the night periods in heating mode. 
RM STPT MIN 
11 
All 
except
 2597  
The minimum temperature setpoint in degrees that the 
controller can use from the setpoint dial. This overrides any 
temperature setpoint from the setpoint dial that falls below this 
minimum. 
RM STPT MAX 
12 
All 
except
 2597 
The maximum temperature setpoint in degrees that the 
controller can use from the setpoint dial. This overrides any 
temperature setpoint from the setpoint dial that falls above this 
maximum. 
RM STPT DIAL 
{13}
2
 
All 
The temperature setpoint in degrees from the room 
temperature sensor (not available on all temperature sensor 
models). This setpoint will be used for control in day mode 
(heating or cooling) when enabled by STPT DIAL. 
STPT DIAL 
14 
All 
except
 2597  
YES indicates that there is a room setpoint dial on the room 
temperature sensor and it should be used as the temperature 
setpoint for control in day/occupied mode. NO indicates that 
the appropriate preset setpoint will be used as the 
temperature setpoint for control in day/occupied heating or 
cooling mode. Valid input: YES or NO. 
AUX TEMP UI 1 
{15} 
All except 2561  
Actual reading from a 10K thermistor connected to the 
controller's Ul 1 input. When a thermistor is connected at Ul 1, 
UI 1 is not available. See UI 1. 
SUPPLY TEMP 
{15} 
2561 
Actual reading from a 10K thermistor connected to the