Chaper 4 – Troubleshooting 
31 
Siemens Industry, Inc. 
BACnet ATEC Owner's Manaul 
125-5050, Rev. AA 
 
4/20/2010 
Safety Features 
The controller board stores the controller's address, applications, and point values. In 
the event of a power failure or a reset, these values are retrieved from the controller's 
permanent memory and are used by the controller unless overridden by a field panel. If 
one of the following conditions occurs, the controller will activate safety features 
present in its fail-safe mode. 
 
Sensor failure. 
 
Loss of power. Upon controller power loss, communication with the controller is 
also lost. The controller will appear as failed (*F*) at the field panel. 
Controller LEDs 
 
 
NOTE: 
The TX and RX LEDs indicate communication over the FLN. 
To determine if the controller is powered up and working, verify that the Basic Sanity 
Test (BST) Light Emitting Diode (LED) is flashing ON/OFF once per second. The 
controller contains seven LEDs located on the circuit board. See the Controller LED 
lndicators [ 12] section of Chapter 1 - Product Overview [ 9] for more information 
about LEDs.