Siemens compact universal controllers 데이터 시트

다운로드
페이지 10
7/10 
Building Technologies 
 
CC1N7865en 
HVAC Products 
 
01.09.2005 
Function of the controller when used for burner control (cont´d) 
 
To acquire the actual value, a number of sensors can be connected to the RWF40... 
 
  
Measurement 
range 
Pt100 / IEC 751 
-200...+850 °C (-328...+1562 °F) 
Pt1000 / IEC 751 
-200...+850 °C (-328...+1562 °F) 
Ni100 / DIN 43760 
-60...+230 °C (-76...+482 °F) 
Ni1000 / DIN 43760 
-60...+230 °C (-76...+482 °F) 
2-or 3-wire resistance 
sensors 
LG-Ni1000 
-50...+160 °C (-58...+320 °F) 
Thermocouples 
NiCr-Ni / type «K» 
-200...+1372 °C (-328...+2502 °F) 
 
Cu-Cu-Ni / type «T» 
-200...+400 °C (-328...+752 °F) 
 
NiCroSil-NiSil / type «N» 
-100...+1300 °C (-148...+2372 °F) 
 
FeCuNi / type «J» 
-200...+1000 °C (-328...+1832 °F) 
 
Pt-RhPt / type «S» 
0...1768 °C (-32...3214 °F) ¹) 
 
Pt-RhPt / type «R» 
0...1768 °C (-32...3214 °F) ¹) 
 
Pt-RhPt / type «B» 
0...1820 °C (32...3308 °F) ¹) 
0...20 mA 
scalable -1999...+9999 
4...20 mA 
scalable -1999...+9999 
DC 0...10 V 
scalable -1999...+9999 
Linearized standard 
signals 
DC 0...1 V 
scalable -1999...+9999 
 
¹) Only RWF40.0X2B97 
 
The power provided for the measuring transducers is DC 24 V / 30 mA. 
 
Feeding a signal to analog input 2, the controller´s setpoint can be influenced. The 
influence can be scaled. 
 
The following signals can be used: 
Input signals DC 0...1 V, DC 0...10 V, 0...20 mA, 4...20 mA 
1 k
Ω potentiometer in a 2-wire circuit 
Analog input 1 (actual 
value sensor) 
Analog input 2 (external 
setpoint shift or external 
setpoint)