The SITRANS LC 500 is easily installed: simply mount the instrument on the process 
connection of the vessel.
Protection for solid-state switch
for dc circuits: connect protection diodes in the correct polarity across the relay coil    
for ac circuits: connect a Voltage Dependent Resistor (VDR) or other ac compatible 
component (such as zeners and protection diodes in combination) in the correct 
polarity across the relay coil
 Process Cautions
Notes: 
• The transmitter is specified for use at temperatures ranging from –40 
°
C to 
85
°
C (–40 
o
F to 185 
o
F): if your process temperature is outside this range, a 
standard option is available with a thermal isolator.
• Before mounting the SITRANS LC 500, check to ensure the threads are 
matching to avoid damaging them. 
? ?
CAUTION: Consider material surface 
configuration when installing unit.
CAUTIONS: 
• With a centrally mounted cable version, 
take care that the tensile load does not 
exceed probe or vessel rating
• With a cable version mounted close to 
the tank wall, take care that the product 
does not push the cable against the tank 
wall: a spring can be used as a retainer.
500 mm
(20”) min.