Chapter 2 - Field Panel Web Server System Administration 
  
Enabling or Disabling Web Server
15
Siemens Industry, Inc. 
 
125-3584T
 
 
 
Be sure that the FPWeb license is installed on the field panel. 
 
 
HMI  
S, H, E, W, M (System, Hardware, Ethernet, Webserver, Modify 
 
 
Example  
10:13:04 07/30/2010 FRI Logged on successfully Field panel 
<40091> 
User: <high> <High default user account> 
 
>Point, Application, Time, Message, Cancel, System, passWord, 
Bye? s 
>Diagnostics, Users, dSt, Bacnet, Error_msgs, Hardware, Text, 
Quit? h 
>Fieldpanels, Ethernet, nodeNametable, Disks, Reportprinter, 
Licensemanager, Quit? e 
>ipSettings, Bbmd, Telnet, Webserver, Quit? w 
>Display, Modify, Uiupgrade, Graphicsbackup, Quit? m 
>Webserver Enabled (Y/N) : y 
>Ok to coldstart (Y/N) : y 
 
Use these procedures to check the enabled/disabled status of Web Server. 
 
HMI  
S, H, E, W, D (System, Hardware, Ethernet, Webserver, Display 
 
 
Example  
10:13:04 07/30/2010 FRI Logged on successfully Field panel 
<40091> 
User: <high> <High default user account> 
>Point, Application, Time, Message, Cancel, System, passWord, 
Bye? s 
>Diagnostics, Users, dSt, Bacnet, Error_msgs, Hardware, Text, 
Quit? h 
>Fieldpanels, Ethernet, nodeNametable, Disks, Reportprinter, 
Licensemanager, Quit? e 
>ipSettings, Bbmd, Telnet, Webserver, Quit? w 
>Display, Modify, Uiupgrade, Graphicsbackup, Quit? d 
Webserver Enabled : Enabled